Chimney Diagram - Vermont Castings Stardance SDDVT Series Installation & Operating Manual

Direct vent gas heater
Hide thumbs Also See for Stardance SDDVT Series:
Table of Contents

Advertisement

H. Chimney Diagram
D
L
A = Clearance above grade, veranda, porch, deck
or balcony
B = Clearance to window or door that may be
opened
C = Clearance to permanently closed window
D = Vertical clearance to ventilated soffit located
above the terminal within a horizontal distance
of 2' (610 mm) from the center line of the
terminal
E = Clearance to unventilated soffit
F = Clearance to outside corner
G = Clearance to inside corner
H = Clearance to each inside of center line
extended above meter/regulator assembly
I =
Clearance to service regulator vent outlet
J = Clearance to non-mechanical air supply inlet
to building or the combustion air inlet to any
other appliance
K = Clearance to mechanical air supply inlet
L = Clearance above paved sidewalk or paved
driveway located on public property
M = Clearance under veranda, porch, deck or
balcony
N = Clearance above a roof shall extend a minimum of 24" (610mm) above the highest point when it passes through the roof surface, and any other obstruction
within a horizontal distance of 18" (450mm).
Figure 2.11 - Vent termination clearances.
1. In accordance with the current CSA-B149 Installation Codes
2. In accordance with the current ANSI Z223.1/NFPA 54 National
Fuel Gas Codes
† A vent shall not terminate directly above a sidewalk or paved
driveway which is located between two single family dwellings
and serves both dwellings
 Only permitted if veranda, porch, deck or balcony is fully open
on a minimum 2 sides beneath the floor.
1111
V
A
E
C
B
B
V
Fixed
Closed
V
Operable
F
V
B
B
CFM145a
VENT TERMINATION
X
AIR SUPPLY INLET
V
CANADIAN INSTALLATIONS
CFM145a
DV Termin Location
12" (30cm)
5/01/01 Rev. 12/05/01
sta
6" (15cm) for appliances <10,000 BTU/h (3kW)
12" (30cm) for appliances >10,000 BTU/h (3kW)
and <100,000 BTU/h (30kW)
36" (91cm) for appliances >100,000 BTU/h (30kW)
12" (305mm) recommended to prevent window
condensation
18" (458mm)
12" (305mm)
see next page
see next page
3' (91cm) within a height of 15' (5m) above the
meter/regulator assembly
3' (91cm)
6" (15cm) for appliances <10,000 BTU/h (3kW)
12" (30cm) for appliances >10,000 BTU/h (3kW)
and <100,000 BTU/h (30kW)
36" (91cm) for appliances >100,000 BTU/h (30kW)
6' (1.83m)
7' (2.13m)
12" (30cm)

Vermont Castings • Stardance SDDVT Installation Manual_R23 • 11/21
INSIDE
CORNER DETAIL
G
H
B
V
Fixed
Closed
B
V
J
X
A
AREA WHERE TERMINAL IS NOT PERMITTED
1
NOTE:
1. Local codes or regulations may require different clearances.
2. The special venting system used on Direct Vent Fireplaces are
certified as part of the appliance, with clearances tested and
approved by the listing agency.
3. HHT assumes no responsibility for the improper performance
of the appliance when the venting system does not meet these
requirements.
N
M
X
I
K
V
US INSTALLATIONS
12" (30cm)
6" (15cm) for appliances <10,000 BTU/h (3kW)
9" (23cm) for appliances >10,000 BTU/h (3kW) and
<50,000 BTU/h (15kW)
12" (30cm) for appliances >50,000 BTU/h (15kW)
12" (305mm) recommended to prevent window
condensation
18" (458mm)
12" (305mm)
see next page
see next page
3' (91cm) within a height of 15' (5m) above the
meter/regulator assembly
3' (91cm)
6" (15cm) for appliances <10,000 BTU/h (3kW)
9" (23cm) for appliances >10,000 BTU/h (3kW) and
<50,000 BTU/h (15kW)
12" (30cm) for appliances >50,000 BTU/h (15kW)
3' (91cm) above if within 10' (3m) horizontally
7' (2.13m)
12" (30cm)

2
3-90-30007467

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents