MAXIMUM/PERCENT HIGH SUBMENU:
Specify in percent, the maximum value (99) for control output. If the output is
analog proportional (Current or Voltage), then the maximum voltage or current, in
percent, is specified. If the output is time proportional (Relay, SSR, or Pulse),
then the maximum duty-cycle, in percent, is specified.
Press d
Press b & c 13) Use b and c buttons to enter a new value for "Percent High".
Press d
Example: On an Analog Output of 0~10 Vdc, a setting of %LO = 10 and %HI = 90,
cause the minimum on the control output to be 1 V and the maximum on the
control output to be 9 V. The same setting on a time proportional output, will
cause 10% duty cycle for the minimum control output and 90% duty cycle for
maximum control output. To disable %LO/HI, set LO to 00 and HI to 99. If %LO/HI
is at other values than the default (%LO = 00, %HI = 99), SOAK is disabled.
CONTROL TYPE OUTPUT:
(Relay, SSR, or Pulse)
Press d
Press b
Press d
The ON/OFF control is a coarse way of controlling the process. The "Dead
Band" improves the cycling associated with the On/Off control.
The PID control is best for processes where the set point is continuously
changing and/or a tight control of the process variable is required. PID control
requires tuning and adjustment of the "Proportional", "Integral or Reset" and
"Derivative or Rate" terms by a trial-and-error method.
The instrument provides an "Auto Tuning" feature making the tuning process
automatic, possibly optimum.
12) Display flashes 1
14) Display shows STRD stored message momentarily and then
advances to CTRL Control Type Submenu.
15) Display flashes ON.OF On/Off or PID Proportional, Integral,
Derivative.
16) Scroll through the available selections: "ON/OFF" or "PID".
17) Display flashes STRD stored message momentarily and
then advances to AçTN only, if it was changed, otherwise press
a to advance to AçTN Action Type Submenu.
st
digit of previous "Percent High" setting.
35