3.2.7 Alarm 2
This unit is equipped with three physical outputs that can only be configured as:
a) Alarm 1, Alarm 2 & Analog Output
b) Output 1, Alarm 2 & Analog Output
Alarm must be DISABLED if Ramp is ENABLED.
ENTER ALARM 2 MENU:
Press a
Press d
Press a
Press d
Alarm 2 menu items are identical to Alarm 1 Menu, except Alarm 2 does
not have Alarm enable/disable at Power On submenu item. Modifying
Alarm Settings will not reset the instrument.
Figure 3.6 Flow Chart for Alarm 2
1) Press a , if necessary, until CNFG prompt appears.
2) Display advances to INPT Input Menu.
3) Press a , if necessary, until Display advances to ALR2 Alarm 2
Menu.
4) Display advances to ABSo Absolute/Deviation Submenu.
30