Omega i Series User Manual page 27

Temperature & process controller
Hide thumbs Also See for i Series:
Table of Contents

Advertisement

ENTER READING CONFIGURATION MENU:
Press a
Press d
Press a
Press d
DECIMAL POINT SUBMENU:
Press d
Press b
Press d
TEMPERATURE UNIT SUBMENU:
Press d
Press b
Press d
FILTER CONSTANT SUBMENU:
Press d
Press b
Press d
1) Press a , if necessary, until CNFG prompt appears.
2) Display advances to INPT Input Menu.
3) Display advances to RDG Reading Configuration Menu.
4) Display advances to DEC Decimal Point.
5) Display flashes previous selection for Decimal location.
6) Scroll though the available selections and choose Decimal
location: FFFF or FFF.F (also FF.FF and F.FFF — if PROC
Process type was selected in the Input Type Menu).
7) Display shows STRD stored message momentarily and then
advances to TEMP Temperature Unit.
Decimal Point for Process Input Type is passive.
8) Display flashes previous Temperature Unit selection.
9) Scroll though the available selections to the Temperature Unit
of your choice: °F or °C .
10) Display shows STRD stored message momentarily and then
advances to FLTR Filter Constant.
11) Display flashes previous selection for Filter Constant.
12) Scroll though the available selections: 0001 , 0002 , 0004 ,
0008 , 0016 , 0032 , 0064 , 0128 . - Default is 0004
13) Display shows STRD stored message momentarily only, if a
change was made, otherwise press a to advance to the next menu.
If Process was selected in the Input Type Menu the display will
advance to IN.RD Input/Reading Submenu, otherwise the
display advances to the ALR1 Alarm 1 Menu.
The Filter Constant Submenu allows the user to specify the
number of readings stored in the Digital Averaging Filter.
For PID control select filter value 0001-0004. A filter value of 2 is
approximately equal to 1 second RC low pass time constant.