Determining The Error From The Status - Omron EJ1 User Manual

Modular temperature controller
Hide thumbs Also See for EJ1:
Table of Contents

Advertisement

Determining the Error from the Status

7-3

Determining the Error from the Status

The EST2-2C-MV3 CX-Thermo Support Software's Status Display can be used to monitor the
EJ1 status and related status in a directory tree.
In addition to the status name and details, possible causes of errors and their countermea-
sures are displayed, which enables efficient processing of errors.
The EJ1 status can be checked by using communications to read the Status.
Status is connected to other status data in a directory tree, so the cause of the
error can be checked or the channels for which there are alarms can be inves-
tigated by searching through the directory tree for the related status.
Example of Using Status Information for Troubleshooting
1. Read the Device A Status (C40000) for the TC4 Unit.
C40000: 'H0004 (i.e., bit 2 is ON)
→ A channel error status bit is ON.
2. Read Error Channel A Status (C4000B).
C4000B: 'H0008 (i.e., bit 3 is ON).
→ An error or alarm has occurred for channel 4.
3. Read the Channel Status (C40401) and Channel Alarm Status (C40402)
of channel 4.
C40401: 'H0001 (i.e., bit 0 is ON)
→ Operation is stopped but there is no input error.
C40402: 'H0003 (i.e., bits 1 and 2 are ON)
→ Channel 4 alarms 1 and 2 are ON.
C4/84 0000
Device A Status
0
Bit 0
Device Error
0
Bit 1
Configuration Error
Bit 2
Channel Error
1
Bit 3
Not used.
0
Bit 4
Expand Communications Error
0
Bit 5
Not used.
0
Bit 6
Not used.
0
Not used.
Bit 7
0
Not used.
0
Bit 8
Not used.
Bit 9
0
I/O Error
Bit 10
0
Lower-level I/O Error
Bit 11
0
I/O Alarm
0
Bit 12
Lower-level I/O Alarm
0
Bit 13
I/O Notification
0
Bit 14
Not used.
Bit 15
0
C4/84 000B
Error Channel A Status
0
Bit 0
CH1
0
Bit 1
CH2
Bit 2
CH3
0
1
Bit 3
CH4
Bit 4
Not used.
0
Bit 5
Not used.
0
Bit 6
Not used.
0
Not used.
0
Bit 7
Bit 8
Not used.
0
Not used.
0
Bit 9
Bit 10
Not used.
0
Bit 11
Not used.
0
0
Bit 12
Not used.
Bit 13
Not used.
0
Bit 14
Not used.
0
Bit 15
Not used.
0
Section 7-3
C4/84 0401
Channel Status
1
RUN/STOP
Bit 0
0
Bit 1
Auto/Manual
Bit 2
AT Execute/Cancel
0
Bit 3
SP Mode
0
Bit 4
Not used.
0
Bit 5
Not used.
0
0
Bit 6
Not used.
Not used.
0
Bit 7
Bit 8
Input Error
0
RSP Input Error
0
Bit 9
Not used.
Bit 10
0
Not used.
Bit 11
0
Bit 12
Not used.
0
Bit 13
Not used.
0
Bit 14
0
Not used.
Bit 15
0
Not used.
C4/84 0402
Channel Alarm Status
Alarm 1
1
Bit 0
1
Alarm 2
Bit 1
Alarm 3
0
Bit 2
Bit 3
Not used.
0
Bit 4
Heater Overcurrent
0
Bit 5
HB Alarm
0
HS Alarm
Bit 6
0
OC Alarm
0
Bit 7
0
Bit 8
Not used.
0
Bit 9
Not used.
Bit 10
Not used.
0
0
Bit 11
Not used.
0
Bit 12
Set Point Limiter Out of Range
Bit 13
0
Set Value Limiter Reverse Operation
0
Bit 14
MV Limiter Reverse Operation
0
Bit 15
Scaling Reverse Operation
167