2. Removal of Electrical Components

Procedure
Step
1. Remove the electrical
component ASSY.
1
Lift and remove the
sound blanket (top).
2
Remove the nut and
remove the terminal
cover.
3
Disconnect the
compressor lead wires
with a flat screwdriver.
Lift and remove the
4
electrical component
ASSY.
Removal Procedure
Warning Be sure to wait for 10 minutes or more after turning off all power
supplies before disassembling work.
Procedure
Electrical component ASSY
Removal of Electrical Components
Sound blanket
(top)
(R11439)
Terminal
cover
(R11440)
Compressor
lead wire
(R11441)
(R11442)
Points
Preparation
Remove the top panel and
disconnect the connector for
the fan motor according to
the "Removal of outer
Panels / Fan Motor".
S(W)
C(U)
R(V)
(R6761)
S(W) : yellow
C(U) : blue
R(V) : red
9