Daikin Siesta Installation Instructions Manual

Daikin Siesta Installation Instructions Manual

Split system

Advertisement

Quick Links

Installation manual
Split system air conditioners
AZQS100B8V1B     
AZQS125B8V1B     
AZQS140B8V1B     
                       
AZQS100B7Y1B     
Installation manual
AZQS125B7Y1B     
English
Split system air conditioners
AZQS140B7Y1B

Advertisement

Table of Contents
loading

Summary of Contents for Daikin Siesta

  • Page 1 Installation manual Split system air conditioners AZQS100B8V1B      AZQS125B8V1B      AZQS140B8V1B                              AZQS100B7Y1B      Installation manual AZQS125B7Y1B      English Split system air conditioners AZQS140B7Y1B...
  • Page 2 2P308775­5D...
  • Page 3: Table Of Contents

    To determine the complete recharge amount ..... reference installation, technical www.daikineurope.com/ 3.4.3 Charging refrigerant: Setup......... guide specifications, reference support­and­manuals/ data,… product­information/. 3.4.4 To charge refrigerant ..........3.4.5 To fix the fluorinated greenhouse gases label .... Latest revisions of the supplied documentation may be available on Connecting the electrical wiring..........the regional Daikin website or via your dealer. 3.5.1 About electrical compliance ........3.5.2 Specifications of standard wiring components.... 3.5.3 To connect the electrical wiring on the outdoor unit..About the box Finishing the outdoor unit installation ........3.6.1 To finish the outdoor unit installation ......3.6.2 To check the insulation resistance of the compressor Outdoor unit 4 Commissioning Checklist before test run............2.1.1 To remove the accessories from the...
  • Page 4: Installation

    3 Installation 3.1.3 To provide drainage Installation Make sure that condensation water can be evacuated properly. INFORMATION Mounting the outdoor unit If necessary, you can use a drain plug kit (field supply) to prevent drain water from dripping. 3.1.1 To provide the installation structure NOTICE Prepare  4  sets  of  anchor  bolts,  nuts  and  washers  (field  supply)  as follows: If drain holes of the outdoor unit are covered by a mounting base  or  by  floor  surface,  raise  the  unit  to  provide  a  free space of more than 150 mm under the outdoor unit. 4× M12 Drain holes (dimensions in mm) (mm) Make sure not to cover the drain holes.
  • Page 5: To Prevent The Outdoor Unit From Falling Over

    3 Installation 5 Do the following: 3.1.4 To prevent the outdoor unit from falling over ▪ Insulate the liquid piping (a) and the gas piping (b). ▪ Wind  heat  insulation  around  the  curves,  and  then  cover  it Connect cables (field supply) as shown: with vinyl tape (c). ▪ Make  sure  the  field  piping  does  not  touch  any  compressor components (d). ▪ Seal the insulation ends (sealant etc.) (e). 4× Connecting the refrigerant piping DANGER: RISK OF BURNING 3.2.1 To connect the refrigerant piping to the 6 If ...
  • Page 6: To Determine If Oil Traps Are Required

    3 Installation 3.2.2 To determine if oil traps are required 3.3.3 To perform vacuum drying If oil flows back into the outdoor unit's compressor, this might cause 1 Vacuum the system until the pressure on the manifold indicates liquid compression or deterioration of oil return. Oil traps in the rising −0.1 MPa (−1 bar). gas piping can prevent this. 2 Leave as is for 4­5 minutes and check the pressure: Then If the pressure… Then… The indoor unit is installed Install an oil trap every 10 m (height Does not change There is no moisture in the higher than the outdoor difference). system. This procedure is unit finished. Increases There is moisture in the system. Go to the next step. 3 Evacuate  for  at  least  2  hours  to  a  pressure  on  the  manifold  of −0.1 MPa (−1 bar).
  • Page 7: Charging Refrigerant: Setup

    3 Installation AZQS140_Y1 3.4.3 Charging refrigerant: Setup Equipment complying with: See "3.3.1 Checking refrigerant piping: Setup" on page 6. ▪ EN/IEC  61000­3­12  provided  that  the  short­circuit  power  S   is greater  than  or  equal  to  the  minimum  S   value  at  the  interface 3.4.4 To charge refrigerant point between the user's supply and the public system. WARNING ▪ EN/IEC  61000­3­12  =  European/International  Technical Standard ...
  • Page 8: Specifications Of Standard Wiring Components

    3 Installation 3.5.2 Specifications of standard wiring components Component AZQS_V1 AZQS_Y1 Power supply cable 29.5 A 31.5 A 32.8 A 15.2 A 17.2 A 21.8 A Voltage 230 V 400 V Phase Frequency 50 Hz Wire sizes Must comply with applicable legislation Interconnection cables Minimum cable section of 2.5 mm² and applicable for 230 V Recommended field fuse 32 A 40 A 16 A 20 A 25 A Earth leakage circuit breaker Must comply with applicable legislation MCA=Minimum circuit ampacity. Stated values are maximum values (see electrical data of combination with indoor units for exact values). 3.5.3 To connect the electrical wiring on the outdoor unit NOTICE ▪ Follow  the  wiring  diagram  (delivered  with  the  unit, located at the inside of the service cover).
  • Page 9: Finishing The Outdoor Unit Installation

    4 Commissioning 1 Measure the insulation resistance over the poles. Connecting to the When cables are routed from the unit, a frame protection sleeve for the conduits (PG Then insertions) can be inserted at the knockout ≥1 MΩ Insulation resistance is OK. This procedure hole. is finished. When you do not use a wire conduit, <1 MΩ Insulation resistance is not OK. Go to the protect the wires with vinyl tubes to next step. prevent the edge of the knockout hole from cutting the wires. 2 Turn ON the power and leave it on for 6 hours. Result:  The  compressor  will  heat  up  and  evaporate  any refrigerant in the compressor. 3 Measure the insulation resistance again. a b c Commissioning A Inside of the outdoor unit B Outside of the outdoor unit NOTICE a Wire NEVER ...
  • Page 10: To Perform A Test Run

    5 Technical data NOTICE To perform a test run ▪ The reversed phase protection detector of this product NOTICE only  functions  when  the  product  starts  up. Consequently  reversed  phase  detection  is  not Do not interrupt the test run. performed during normal operation of the product. ▪ The  reversed  phase  protection  detector  is  designed  to INFORMATION stop  the  product  in  the  event  of  an  abnormality  when In ...
  • Page 11 5 Technical data F1U~F8U ▪ F1U~F4U: Fuse Z1C~Z6C Noise filter (ferrite core) Z1F~Z6F Noise filter (AZQS125+140_V1) ▪ F6U: Fuse (T 5.0 A / 250 V) ▪ F7U, F8U: Fuse (F 1.0 A / 250 V) Symbols: F1U~F8U ▪ F1U, F2U: Fuse (31.5 A / 250 V) Live (AZQS_Y1) ▪ F1U (A2P): Fuse (T 5.0 A / 250 V) Neutral ▪ F3U~F6U: Fuse (T 6.3 A / 250 V) Field wiring ▪ F7U, F8U: Fuse (F 1.0 A / 250 V) Terminal strip H1P~H7P Light­emitting diode (service monitor is Connector orange) Relay connector Light­emitting diode (service monitor is Connection green) Protective earth K1M, K11M Magnetic contactor Noiseless earth Magnetic relay (Y1S) Terminal (AZQS_V1)
  • Page 12 4P385528-1 0000000T 4P385528­1  2014.08...

Table of Contents