Sanyo SPW-XR253GH56 Technical Data & Service Manual page 61

Table of Contents

Advertisement

1-3 Other Component Specifications
Outdoor Unit
MODEL NO.
Power Transformer
Rated
Primary
Secondary
Coil resistance
Thermal cut off temperature
Thermistor (Coil sensor) : TH7
Coil resistance
Thermistor (Discharge gas sensor) : TH8
Coil resistance
Relay (Comp. Magnetic Contactor)
Coil rated
Contact rating
Coil resistance (at 25 °C)
1
Solenoid coil or 4 way valve
4 way valve
Solenoid coil
1 2
3
4
5
Outdoor Unit
VAC, Hz
WHT – WHT : 300
°C
kΩ
kΩ
VAC
VAC, A
SPW-CR253GL5, SPW-CR253GL8
ATR - I65B
230 V, 50 Hz
14 V, 0.4 A
,
145
PBC - 41E - S4
–10 °C : 23.7
,
– 5 °C : 18.8
,
0 °C : 15.0
,
5 °C : 12.1
,
PTC - 51H - S1
60 °C : 13.8
,
70 °C : 9.7
,
75 °C : 8.2
,
80 °C : 7.0
,
85 °C : 5.9
,
FC - 1SZ607
220 - 240 V
440 V, 13 A
I - 56
1. Specifications
BRN – BRN : 2.2
10 °C : 9.7
20 °C : 6.5
30 °C : 4.4
40 °C : 3.1
45 °C : 2.6
90 °C : 5.1
100 °C : 3.8
110 °C : 2.8
120 °C : 2.2
130 °C : 1.7
SM830080

Hide quick links:

Advertisement

Table of Contents
loading