(J) Change the period of the filter timer
If the period of filter timer is not suitable (for example in case of dirty environment),
the period can be shortened to half as follows:
a Press the TEST / CHK button for more than 4 seconds.
AIR FLOW
UNIT
UNIT No.
R.C.
FLAP
TIMER SET
SET
CL
b In case of group control, if you want to change all units in group control collectively,
proceed next step remaining "ALL" displayed.
If you want to change a unit individually, select the indoor unit address (UNIT No.) with
UNIT button.
c Select the CODE No. 02 with
d Change the No. from 0 to 1 with
AIR FLOW
UNIT
UNIT No.
R.C.
FLAP
TIMER SET
SET
CL
e Press the SET button.
CODE No. 06, SET DATA and
f If you made a mistake, press the CL button.
g Finally, press the TEST / CHK button.
MODE
No.
SET TEMP.
CODE
No.
FAN SPEED
SETTING
SET
DATA
ON
OFF
TEST / CHK
0213_M_I
,
(SET TEMP) button.
,
MODE
No.
SET TEMP.
CODE
No.
SET TEMP.
FAN SPEED
SETTING
SET
DATA
ON
OFF
TEST / CHK
0214_M_I
change from flashing to ON state.
SETTING
IV - 35
(
) button.
EX:
UNIT No. 1–6
CODE No. 02
T type 150 hr
4. Service procedures
75 hr
SM830080