1-2 Major Component Specifications
(B) Outdoor Unit
MODEL No.
Source
Controller P.C.B. Ass'y
Control circuit fuse
Compressor
Model ..... number
Source
Nominal output
Compressor oil
Coil resistance
(Ambient temperature 25 °C)
Safety devices
Overload relay models
Operating temperature
Crank case heater
Refrigerant amount at shipment
High pressure switch
Set pressure
Fan
1
Number...diameter
Air circulation (Hi)
Fan speeds
Fan motor
Model
1 2
Source
No. of pole ..... rpm (230V, High / Med. / Low)
Nominal output
Coil resistance
(Ambient temperature 20°C)
Safety device
Operating temperature
3
Run capacitor
Heat exchange
Coil
Rows ..... fin pitch
4
Face area
5
W
cc
°C
Open
°C
Close
kg
OFF kg/cm
2
ON
kg/cm
2
mm
m
3
/h
W
WHT – BRN
WHT – VLT
°C
Open
°C
Close
µF
VAC,
mm
m
2
I - 48
1. Specifications
SPW-CR253GL8
380 - 400 - 415 V / 3 phase / 50 Hz
CR - CR483GHL8 (Microprocessor)
250 V, 3.15 A
Rotary (Hermetic)
C - RN223H8D
380 - 400 - 415 V / 3 phase / 50 Hz
2400
1350
T – R : 5.77
,
R – S : 5.66
S – T : 5.38
Internal type
120 ± 5
98 ± 11
240V, 25 W
R407C - 3.2
ACB - 1TB07
+ 0
+ 0
32
(3.2
– 1.5
– 0.15
24 ± 2.0 (2.4 ± 0.2 MPa)
Propeller
1 ..... ø460
45
3 (AUTO)
KFC6T - 91C5P
220 - 230 - 240 V / 1 phase / 50 Hz
6...772 / 376 / 252
70
: 127.3
,
VLT – YEL
:
56.7
,
YEL – PNK
Internal type
130 ± 8
79 ± 15
440 V, 6 µF
Aluminium plate fin / Copper tube
2 ..... 1.8
0.616
MPa)
:
15.0
:
7.2
SM830080