Sanyo SPW-XR253GH56 Technical Data & Service Manual page 104

Table of Contents

Advertisement

1-11 Installation Instructions
Tubing Length
(A) Single type
Refrigerant tubing between the indoor and
outdoor units should be kept as short as
possible.
The length of the refrigerant tubes between
the indoor and outdoor units are limited by the
elevation difference between the two units.
During tubing work, try to make both the
tubing length (L) and the difference in eleva-
tion (H) as short as possible. Refer to Table
1-1 for the details.
Table 1-1
(R407C Models)
Tubing Data
Tubing size
Narrow tube
outer diameter
Wide tube
Limit of tubing length
Outdoor unit is placed
Limit of elevation
upper
difference between
Outdoor unit is placed
the two units
lower
Max. allowable tubing length at shipment (m)
Required additional refrigerant *
Refrigerant charged at shipment
No additional charge of compressor oil is necessary.
1
*
If total tubing length becomes 30 to 50 m, charge additional refrigerant (R407C) by a) 45 or b) 50 g/m.
Models
SPW-CR253G(H)L5
CR253G(H)L8
mm (in.)
6.35 (1/4)
mm (in.)
15.88 (5/8)
(m)
50
50
(m)
30
(m)
30
1
(g/m)
a) 45
(kg)
3.2
I - 99
1. Specifications
Installation Example 1
Tubing length (L)
INDOOR
UNIT
Elevation difference (H)
OUTDOOR
UNIT
SPW-CR363G(H)L8 SPW-CR483G(H)L8
9.52 (3/8)
19.05 (3/4)
50
50
30
30
b) 50
4.0
0419_M_I
9.52 (3/8)
19.05 (3/4)
50
50
1
30
30
b) 50
4.5
2
3
4
5
SM830080

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents