1-3 Other Component Specifications
Concealed Duct Type
MODEL NO.
Indoor Unit
Power Transformer
Rated
Primary
Secondary
Coil resistance
Thermal cut off temperature
Thermistor (Coil sensor) : TH2, 3, 4
Resistance
Thermistor (Room sensor) : TH1, 5
Resistance
Electronic expansion valve
Valve body
Coil
Drain pump
Rated
Float switch
Rated (Contact rated)
VAC, Hz
WHT –WHT : 110
RED – RED : 2.3
˚ C
-10 ˚C : 23.7 ± 5 %
KΩ
-5 ˚C : 18.8 ± 5 %
0 ˚C : 15.0 ± 5 %
5 ˚C : 12.1 ± 5 %
10 ˚C : 9.7 ± 5 %
0 ˚C :16.5 ± 5 %
KΩ
5 ˚C :12.8 ± 5 %
10 ˚C :10.0 ± 5 %
20 ˚C : 6.3 ± 5 %
30 ˚C : 4.0 ± 5 %
IKV-24D12 (SPW-UR253GHN56)
HKV-30D16 (SPW-UR363 · 483GHN56)
DKV-MOZS697E0 (SPW-UR253GHN56)
EKV-MOZS698E0 (SPW-UR363 · 483GHN56)
I - 55
1. Specifications
SPW-UR253 ~ 483GHN56
ATR-II215TB
230 V, 50 Hz
10.2 V 1.4 A
14 V 0.5 A
,
BRN – BRN : 0.5
145
PBC-41E-S36 , PBC-41E-S25
20 ˚C : 6.5 ± 5 %
,
30 ˚C : 4.4 ± 5 %
,
40 ˚C : 3.1 ± 5 %
,
45 ˚C : 2.6 ± 5 %
,
KTEC-35-S6, KTEC-35-S85
40 ˚C : 2.7 ± 5 %
,
45 ˚C : 2.2 ± 5 %
,
50 ˚C : 1.8 ± 5 %
,
55 ˚C : 1.5 ± 5 %
,
PTV-1422
AC 230 V, 12 W
FS-0218-103
DC 12 V, 25 W
1
2
3
4
5
SM830080