Device Configuration (Address 1000); Ct Conf - Siemens ISGS Operator's Manual

Intelligent switchgear system
Hide thumbs Also See for ISGS:
Table of Contents

Advertisement

3
Operation
Major Addr. Bl ock
Function
Required operation
steps
Remarks
1-3
1-9
1-14
7100
Parameter sets (ncrmaValtemate)
./
7200
Commlrications port configlJ'atbn
./
8100
Tine
and date setting
./
Skip step
8.
See
deta~s
for data for-
mat. Message at step
7
is "CLCCK
ADJLSTED."
8200
Reset (trip bg, rrin/max, energy)
./
Skip steps
6-7.
Messages at step
8
are "IN
PROGRESS"
and "SUC-
CESSFUL."
Ja:m
Breaker monitoring configlJ'ation
./
,
8400
Waveform captlJ'e configuration
Note
1 : Do
not change configuration while
the
relay is in serke. Olanging configuration causes reinitialization time of up to
~
seconds.
DlJ'Ing reu"Vtlahzatbn, the relay cbes not piOVlde protectbn.
Table 3.5
Major Address Block Operation Steps
(Contirued)
3.7.1
Device Configuration (Address 1000)
Use this address block to configure the ISGS relay to match
the line frequency, phase
sequence, and
breaker connection
settings fcr your system. The
ava~able
relay subaddresses
are listed in Table 3.6. To make parameter changes, yoo
rTILSt trst enter the passwcrd. If you orty want to review the
present settings, the password steps 4 and 5 are not neces-
sary.
Perform parameter changes using steps 1-9 of the
standard operation sequence, Toole 3.4.
Note:
Do not change device configuration (Table 3.6)
wh~e
the relay is in service, as the relay can require up to 30 sec-
onds to reinitialize for this change. Durng reinitialization, the
relay does not provide protection.
Subaddress
Parameter
Selection
1002
Frequency
60Hz
or
50Hz
1003
Phase Sequence
123
{ABC) or
132
{ACB)
1004
Breaker Comection Trip
1
or Trip
2
Table 3.6
DeviCe Configuration, Ma]O( Block 1000
The breaker connection parameter
(1
004) defines which
ootput contact (Trip
1
or Trip 2) is connected to open the cir-
cuit breaker. This information is used by the breaker failre
ft.nction,
if
that ft.nction is enabled (see section 3. 7 .14).
Also, refer to the discussion on matrixing in section 3.
11
.
3.7.2
CT Configuration (Address 1100)
Use this address block to configure the ISGS relay to match
the Phase
CT
Primary Rating and Neutral or Grot.nd
CT
Pri-
mary Rating settings, and the
CT
input's Norm Power Row
settings to match your system. The available relay subad-
dresses are listed in Table 3.7.
Siemens Energy & Automation, Inc.
To make parameter changes, you must first enter the
pass-
word.
If
you only want to review present settings, the pass-
word steps 4 and 5 are not
necessary
Perform parameter
changes using steps 1-9
of
the standard operation
sequence, Toole 3.4.
Note:
Do not change
CT
configuration (Table 3.7)
wh~e
the
relay is in service, as the relay can require up to 30 seconds
to reinitialize for this change. During reinitialization, the relay
does not provide protection.
Subaddress
Parameter
Selection
1101
Phase CT Prinary
5- 8000A
Rating
1102
Neutral cr Ground
5- 8000A
CT Primary Rating
1104
Normal Power Row
Normal or Reverse
Table 3.7 CT
ConfiQuratlon, Major Block 1100
The phase
(11
0 1) and neutraVgrot.nd (1102)
CT
primary rat-
ings are independently configurable. However, when a resid-
ual sensing method is used for ground taut protection, the
primary current ratings for the neutral
CT
and the phase
CT
must be equal.
Power flow conventions (1104) are defned such that "Nor-
mal" power low is into the phase
CT
polarity mark, and
"Reverse" power ftow is out
of
the phase
CT
polarity mark.
Figure 3.2 illustrates exafll)les
of
normal and reverse power
flow.
19

Advertisement

Table of Contents
loading

Table of Contents