Handling Unit After Removal From Skid; General; Minimum Installation Height; Figure 4 Unit On Appliance Cart - Bard Q-TEC Q24H3DA Installation Instructions Manual

Packaged heat pump
Hide thumbs Also See for Q-TEC Q24H3DA:
Table of Contents

Advertisement

HANDLING UNIT AFTER REMOVAL
FROM SKID
WARNING
Exercise extreme caution when pushing the
unit on the rollers. Handle and push from the
lower 1/3 of the unit. Insure that debris is not
on the floor where the unit is to be moved on
the rollers. Failure to do so could result in the
unit tipping over and causing bodily injury and/
or damage to the unit.
The unit will have to be turned sideways and removed
from the skid to fit through a 36" doorway. If the door
height allows, the unit can be slid sideways through the
door.
If the unit can not be slid through the door, then the
unit will have to be put on a cart and tipped down
to roll through the door. It is recommended that an
appliance cart by used with a strap to hold the unit on
the cart. The wheels of the unit must be locked. If the
wheels were allowed to roll, the unit could roll off the
cart. The unit should always be carted from the left
side. This is the side where the compressor is located
(see Figure 4). The blade of the appliance cart should
be slid under the wheels of the unit. The strap of the
appliance cart should be placed around the unit and
strapped tightly. Help will be required to tip the unit
back onto the cart. The unit can be leaned far enough
FIGURE 4
Unit on Appliance Cart
Appliance
Cart
Compressor
Manual 2100-653
Page
8 of 44
back to be rolled through the door. Be careful when
setting the unit back up to keep from damaging the
unit.

GENERAL

The equipment covered in this manual is to be installed
by trained, experienced service and installation
technicians.
The unit is designed for use with or without duct work.
For use without duct work, Plenum Box QPB42 is
recommended.
These instructions explain the recommended method
to install the air cooled self-contained unit and the
electrical wiring connections to the unit.
These instructions and any instructions packaged with
any separate equipment required to make up the entire
air conditioning system should be carefully read before
beginning the installation. Note particularly "Start
Procedure" and any tags and/or labels attached to the
equipment.
While these instructions are intended as a general
recommended guide, they do not supersede any
national and/or local codes in any way. Authorities
having jurisdiction should be consulted before the
installation is made. See page 3 for information on
codes and standards.
Size of unit for a proposed installation should be based
on heat loss calculation made according to methods
of Air Conditioning Contractors of America (ACCA).
The air duct should be installed in accordance with
the Standards of the National Fire Protection Systems
of Other Than Residence Type, NFPA No. 90A, and
Residence Type Warm Air Heating and Air Conditioning
Systems, NFPA No. 90B. Where local regulations are
at a variance with instructions, installer should adhere
Q-TEC Unit
to local codes.
(Right Side)

MINIMUM INSTALLATION HEIGHT

The minimum installation height of the unit with a Free
Blow Plenum is 8' 6". This provides enough clearance
for the plenum to be removed (see Figure 5).
Strap
The minimum installation height for ducted
applications is 8' 4½". This provides enough clearance
to install the duct work (see Figure 6).

Advertisement

Table of Contents
loading

Table of Contents