CONTENTS Getting Other Information and Publications ..3 tart Up ................ 27 R-410A Refrigerant: General ........27 Q-TEC Series General Information ......4 Topping Off System Charge ........27 Q-TEC Model Nomenclature ........4 Safety Practices ............. 27 Shipping Damage ............. 7 Description of Standard Equipment ......
GETTING OTHER INFORMATION AND PUBLICATIONS These publications can help when installing the air For more information, contact these publishers: conditioner or heat pump. They can usually be found at a local library or can be purchased directly from the ACCA Air Conditioning Contractors of America publisher.
Q-TEC Series General Information Q-TEC MODEL NOMENCLATURE MODEL HEAT NUMBER FILTER OPTIONS 0Z - 0KW PUMP X - 1" Fiberglass COIL OPTIONS 05 - 5KW INTERNAL (Standard) X - Standard 06 - 6KW CONTROLS REVISION F - 2" Fiberglass 1 - Phenolic coated CAPACITY 09 - 9KW X - Standard...
TABLE 2 – Electrical Specifications Single Circuit Dual Circuit Minimum Maximum Rated Volts Field Maximum Circuit External Fuse or Field Power Ground MODEL Minimum Field & Phase Power External Ground Ampacity Ckt. Breaker Wire Size Wire Size Circuit...
SHIPPING DAMAGE FIGURE 2 Air Seal Under Q-TEC Unit Upon receipt of equipment, the carton should be checked for external signs of shipping damage. The skid must remain attached to the unit until the unit is ready for installation. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
HANDLING UNIT AFTER REMOVAL back to be rolled through the door. Be careful when setting the unit back up to keep from damaging the FROM SKID unit. WARNING GENERAL The equipment covered in this manual is to be installed Exercise extreme caution when pushing the by trained, experienced service and installation unit on the rollers.
DUCT WORK For hot water coil option, a QPBHWxx-F for free blow or QPBHWxx-D for ducted airflow is used. Any heat pump is more critical of proper operating When used with a ducted supply, a QCX Cabinet charge and an adequate duct system than a straight air Extension can be used to conceal the duct work above conditioning unit.
This fresh air assembly is located in the An optional rear drain kit, Bard Model QCDS48A, is rear of the unit and to gain access to make these also available for these products. The optional rear adjustments remove the air filter service door.
FIGURE 9 FIGURE 10 Optional Side Drain (Side View) Standard Rear Drain Q-TEC UNIT FIGURE 11 Rear Drain (Top View) Drain Line Wall (maximum 10" for rear drain) Sleeve Couplings not shown but recommended for ease of removability for service Wall Bracket Water...
FIGURE 12B PLUG INSTALLED IN SIDE Q/Tec DRAIN REAR DRAIN CONNECTION IN Q/Tec PRODUCT IMPORTANT! 1/2" SLIP X 1/2" SLIP X 3/4" NPT TEE SUPPLIED WITH DRAIN BOX KIT 3/4" PLASTIC PIPE NIPPLE (TIGHTEN THREADS SO TEE IS SUPPLIED WITH DRAIN BOX KIT HORIZONTAL TO FLOOR) (APPLY TEFLON TAPE TO THREADS)
FIGURE 12D DRAIN HOSE FROM INDOOR DRAIN PAN. MOVE HOSE FROM ATTACHMENT IN LOWER DRAIN PAN AND SLIDE ONTO DRAIN BOX BARB FITTING, SECURING WITH SUPPLIED CLAMP IF OUTDOOR PAN IS BYPASSED. ( WILL REDUCE RISK OF ALGAE GROWTH IN THE OUTDOOR PAN BUT AT A SLIGHT COOLING PERFORMANCE REDUCTION OF 2-3% ) MIS-2472...
FIGURE 13A Unit Mounting – Method 1 Side Trim (2 PCS.) Enlarged view of mounting bracket showing sleeve to cabinet attachment Side Trim (2 PCS.) Mounting Bracket Wall Sleeve #8 Screw Provided (Light Color) Mounting Bracket Cabinet Side Panel #10 Hex Head Screw Bottom Trim Provided...
INSTALLATION MOUNTING THE UNIT centered in the sleeve. Also check the alignment to the mounting brackets. This unit must be level When installing a Q-TEC unit near an interior wall on from side to side. If adjustments are necessary, the left side, a minimum of 8" is required but 12" is shim up under the rollers with sheets of steel or preferred.
WIRING – MAIN POWER The field wiring connections are located behind the top and hinged panel in the circuit breaker panel (see Refer to the unit rating plate and/or Table 2 for wire Figure 15). sizing information and maximum fuse or circuit breaker size.
the electric heaters will turn off and the airflow will be dehumidification and the unit will cool until the thermostat reduced and the system will continue to dehumidify until is satisfied. Once the call for cooling is satisfied, the unit humidistat is satisfied.
GENERAL “F” terminal of pin 5 of P2 is the ventilation input. This terminal energizes any factory installed ventilation This unit is equipped with a variable speed ECM motor. option. The motor is designed to maintain rated airflow up to NOTE: For total and proper control using DDC, a total the maximum static allowed.
TOPPING OFF SYSTEM CHARGE 9. Never heat cylinders above 125°F. 10. Never trap liquid R-410A in manifold sets, gauge If a leak has occurred in the system, Bard lines or cylinders. R-410A expands significantly Manufacturing recommends reclaiming, evacuating at warmer temperatures. Once a cylinder or line is...
DESCRIPTION OF STANDARD PHASE MONITOR EQUIPMENT All units with three phase scroll compressors are equipped with a three phase line monitor to prevent Solid State Electronic Heat Pump Control compressor damage due to phase reversal. Provides efficient 30-minute defrost cycle. A The phase monitor in this unit is equipped with two thermistor sensor and speed up terminal for service LEDs.
SERVICE HINTS 7. Annual maintenance is required to ensure that all of the systems are functioning properly. 1. Caution user to maintain clean air filters at all Check to make sure that the drains are not times and to not needlessly close off supply air obstructed in any way.
VENT OPTIONS Q-TEC Energy Recovery Ventilator (Option) Before starting, make sure that the power has been Barometric Fresh Air Damper (Standard) turned off. The return air grille panel must be Before starting, make sure the power has been turned removed. The energy recovery ventilator (QERV) can be off.
SEQUENCE OF OPERATION coil when it is inactive. This drain does not affect the normal operation of the system. Cooling – Circuit R-Y makes the thermostat pull in There is a check valve located in the reheat coil the compressor contactor starting the compressor return line.
REFRIGERANT TUBE SCHEMATIC FOR REHEAT COIL Figure 25 shows the refrigerant gas flow through the reheat coil during the dehumidification mode. When the unit is in standard cooling (Figure 26) or heating mode, the reheat coil is inactive. FIGURE 25 Q-TEC Dehumidification Mode Circuit Diagram Manual 2100-653 Page...
FIGURE 26 Q-TEC Cooling Mode Circuit Diagram PRESSURE SERVICE PORTS WARNING! Do NOT use a Schrader valve core removal tool with these valves. Use of such a tool could result High and low pressure service ports are installed on in eye injuries or refrigerant burns! all units so that the system operating pressures can To change a Coremax valve without first removing the be observed.
DEFROST CYCLE There is an initiate defrost jumper (sen jump) on the control that can be used at any outdoor ambient during The defrost cycle is controlled by temperature and time the heating cycle to simulate a 0° coil temperature. on the solid state heat pump control.
TROUBLESHOOTING SOLID STATE HEAT PUMP CONTROL 3. Turn thermostat blower to “auto” position. Indoor blower should stop. NOTE: Many models have a TROUBLESHOOTING PROCEDURE 1-minute blower time delay on “off” command; NOTE: A thorough understanding of the defrost wait for this to time-out. cycle sequence is essential.
CHECKING TEMPERATURE SENSOR 4. If sensor resistance reads very low, then sensor is shorted and will not allow proper operation of the 1. Disconnect temperature sensor from board and heat pump control. from outdoor coil. 5. If sensor is out of tolerance, shorted, open or reads 2.
TROUBLESHOOTING ECM ™ BLOWER MOTORS CAUTION: Symptom Cause/Procedure • Noisy blower or cabinet • Check for loose blower housing, panels, etc. Disconnect power from unit before removing or replacing • High static creating high blower speed? connectors, or servicing motor. To avoid electric shock - Check for air whistling through seams in ducts, cabinets or panels from the motor’s capacitors, disconnect power and wait at...
TROUBLESHOOTING GE ECM ™ MOTORS CONT’D. 8b. IF REPLACING AN ECM 2.3 CONTROL WITH AN ECM 2.3 Replacing ECM Control Module CONTROL, the plastic tab and shorter through-bolts are not needed. The Replacing ECM Control Module 8b. IF REPLACING AN ECM 2.3 CONTROL WITH AN ECM 2.3 To replace the control module for the GE variable-speed indoor blower control can be oriented in two positions 180°...
FAN BLADE SETTING DIMENSIONS R-410A REFRIGERANT CHARGE Any service work requiring removal or adjustment in the This unit was charged at the factory with the quantity fan and/or motor area will require that the dimensions of refrigerant listed on the serial plate. AHRI capacity in Table 7 be checked and blade adjusted in or out of and efficiency ratings were determined by testing with the motor shaft accordingly.
TABLE 10 Cooling Pressure (All Temperatures in Degrees F) RETURN AIR TEMPERATURE ENTERING OUTDOOR COIL MODEL PRESSURE 75° 80° 85° 90° 95° 100° 105° 110° 115° 120° TEMP. 75 DB Low Side 62 WB High Side 80 DB Low Side Q24H3D 67 WB High Side...
TABLE 11 Heating Pressure (All Temperatures in Degrees F) RETURN AIR TEMPERATURE ENTERING OUTDOOR COIL MODEL PRESSURE TEMP. Low Side Q24H3D High Side Low Side Q30H3D High Side Low Side Q36H3D High Side Low Side Q43H3D High Side Low Side Q48H3D High Side Low Side...