Shipping And Storage Conditions; Mechanical And Climatic Ambient Conditions - Siemens S7-1500 Manual

Simatic top connect
Hide thumbs Also See for S7-1500:
Table of Contents

Advertisement

Technical specifications

6.3 Shipping and storage conditions

6.3
Shipping and storage conditions
Introduction
SIMATIC TOP connect system cabling meets IEC 61131-2 requirements for shipping and
storage conditions. The specifications below apply to modules that are shipped or stored in
their original packaging.
Shipping and storage conditions for modules
Type of condition
Drop test (in transport package)
Temperature
Air pressure
Relative humidity
Sinusoidal vibrations in accordance with IEC
60068-2-6
Shock conforming to IEC 60068-2-27
6.4

Mechanical and climatic ambient conditions

Operating conditions
SIMATIC TOP connect system cabling is designed for stationary use in weather-proof
locations. The conditions of use meet the requirements of DIN IEC 60721-3-3:
● Class 3M3 (mechanical requirements)
● Class 3K3 (climatic requirements)
52
Permissible range
≤1 m
From -40 °C to +70 °C
From 1080 to 660 hPa (corresponds to an
altitude of -1000 to 3500 m)
5% to 95%, without condensation
5 to 9 Hz: 3.5 mm
9 to 500 Hz: 9.8 m/s²
250 m/s², 6 ms, 1000 shocks
SIMATIC TOP connect for S7-1500 and ET200MP
Manual,

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Et200mp

Table of Contents