To operate SIMATIC TOP connect system cabling and S7-300 automation systems in a
residential area, the RF emission must comply with Limit Value Class B to EN 55011. Suitable
measures for achieving RF interference Limit Class B include, for example:
● Fitting the cabling system and automation system in grounded control cabinets/control
boxes
● Use of noise filters in the supply lines
6.2
Electromagnetic compatibility
Definition
Electromagnetic compatibility (EMC) is the capacity of an electrical installation to function
satisfactorily in its electromagnetic environment without affecting that environment.
SIMATIC TOP connect system cabling also meets the requirements of EMC legislation for the
European internal market in addition other requirements. This requires the S7-300 system to
meet the specifications and directives for electrical installation.
6.3
Shipping and storage conditions
Introduction
SIMATIC TOP connect system cabling meets IEC 61131-2 requirements for shipping and
storage conditions. The following information applies to modules that are shipped and/or stored
in their original packaging.
Shipping and storage conditions for modules
Type of condition
Drop test (in transport package)
Temperature
Air pressure
Relative humidity
Sinusoidal oscillation
to IEC 60068-2-6
Shock conforming to IEC
60068-2-27
System cabling for S7-300
Manual, 09/2018, 70327045899
Permissible range
≤1 m
From -40 °C to +70 °C
From 1080 to 660 hPa (corresponds to an altitude of -1000 to 3500
m)
5% to 95%, without condensation
5 to 9 Hz: 3.5 mm
9 to 500 Hz: 9.8 m/s²
250 m/s², 6 ms, 1000 shocks
Technical specifications
6.3 Shipping and storage conditions
61