16 Unit installation

In this chapter

16.1 Preparing the installation site

16.1.1 Installation site requirements of the indoor unit

FXFN50~112A2VEB
CO₂ Conveni-Pack: indoor unit
4P677925-1 – 2021.07
WARNING
Installation shall be done by an installer, the choice of materials and installation shall
comply with the applicable legislation. In Europe, EN378 is the applicable standard.
WARNING
Make sure to install all necessary countermeasures in case of refrigerant leakage
according to standard EN378 (see
requirements for CO₂
Make sure to install a CO
refrigerant leak detection (see
16.1
Preparing the installation site ................................................................................................................................................
16.1.1
Installation site requirements of the indoor unit ..................................................................................................
16.1.2
Additional installation site requirements for CO₂ refrigerant...............................................................................
16.2
Mounting the indoor unit.......................................................................................................................................................
16.2.1
Guidelines when installing the indoor unit............................................................................................................
16.2.2
Guidelines when installing the drain piping ..........................................................................................................
Choose an installation location with sufficient space for carrying the unit in and out
of the site.
Avoid installation in an environment with a lot of organic solvents such as ink and
siloxane.
Do NOT install the unit in places often used as work place. In case of construction
works (e.g. grinding works) where a lot of dust is created, the unit MUST be
covered.
INFORMATION
Also read the general installation site requirements. See the
4
precautions" [
INFORMATION
The sound pressure level is less than 70 dBA.
CAUTION
Appliance NOT accessible to the general public, install it in a secured area, protected
from easy access.
This unit, both indoor and outdoor, is suitable for installation in a commercial and
light industrial environment.
Do NOT install the unit in the following places:
In places where a mineral oil mist, spray or vapour may be present in the
atmosphere. Plastic parts may deteriorate and fall off or cause water leakage.
4
refrigerant" [
 50]).
leak detector (field supply) and enable the function for
2
"20.1 Field
 5]" chapter.
16
Unit installation
|
"16.1.2  Additional installation site
setting" [
4
 74]).
""2  General safety
Installer and user reference guide
47
47
50
54
54
57
47