For The Installer; About The Box; Indoor Unit; To Remove The Accessories From The Indoor Unit - Daikin FXFN50A2VEB Installation And Operation Manual

Table of Contents

Advertisement

For the installer

11

About the box

11.1

Indoor unit

11.1.1
To remove the accessories from the
indoor unit
a
b
h
a
Paper pattern for installation (top part of packing box)
b
General safety precautions
c
Indoor unit installation and operation manual
d
Installation guide
e
Washers for hanger brackets
f
Screws (to temporarily attach the paper pattern for
installation to the indoor unit)
g
Tie wraps
h
Metal clamp
i
Sealing pads: Large (drain pipe), medium 1 (gas pipe),
medium 2 (liquid pipe), small (electrical wiring)
j
Drain hose
k
Power supply cable
l
Communication cable
m
Insulation piece: Small (liquid pipe)
n
Insulation piece: Large (gas pipe)
o
Insulation piece (drain pipe)
12

Unit installation

WARNING
Installation shall be done by an installer, the choice of
materials and installation shall comply with the applicable
legislation. In Europe, EN378 is the applicable standard.
WARNING
▪ Make sure to install all necessary countermeasures in
case of refrigerant leakage according to standard
EN378
(see
"12.1.2  Additional
requirements for CO₂
▪ Make sure to install a CO
and enable the function for refrigerant leak detection
setting" [ 4  22]).
(see
"16.1 Field
FXFN50~112A2VEB
CO₂ Conveni-Pack: indoor unit
3P672850-1A – 2021.07
c
d
e
f
i
j
k
l
m
n
o
installation
site
refrigerant" [ 4  14]).
leak detector (field supply)
2
12.1

Preparing the installation site

Avoid installation in an environment with a lot of organic solvents
such as ink and siloxane.
12.1.1
Installation site requirements of the
indoor unit
INFORMATION
g
The sound pressure level is less than 70 dBA.
CAUTION
Appliance NOT accessible to the general public, install it in
a secured area, protected from easy access.
This unit, both indoor and outdoor, is suitable for
installation
in
environment.
NOTICE
This is a class A product. In a domestic environment this
product may cause radio interference in which case the
user may be required to take adequate measures.
▪ Spacing. Mind the following requirements:
a
A
A
Minimum distance to the wall (see below)
B
Minimum and maximum distance to the floor (see below)
C
50~71 class:
≥269 mm: In case of installation with standard decoration
panel
≥311 mm: In case of installation with design decoration
panel
≥349 mm: In case of installation with self-cleaning
decoration panel
≥319 mm: In case of installation with standard panel +
fresh air intake kit
≥361 mm: In case of installation with design panel + fresh
air intake kit
112 class:
≥311 mm: In case of installation with standard decoration
panel
≥353 mm: In case of installation with design decoration
panel
≥391 mm: In case of installation with self-cleaning
decoration panel
≥361 mm: In case of installation with standard panel +
fresh air intake kit
≥403 mm: In case of installation with design panel + fresh
air intake kit
a
Indoor unit
b
Lighting (the figure shows ceiling-mounted lighting, but
recessed lighting is also allowed)
c
Air fan
d
Static volume (example: table)
11 About the box
a
commercial
and
light
b
c
a
≥1500
≥2000
≥4000
Installation and operation manual
industrial
d
(mm)
13