7.7.4 CGWF HE high head pressure pumps characteristics
CGWF HE USER SIDE (CXWF SOURCE SIDE)
Mod.
CGWF
CXWF
HE
055
060
060
070
070
080
085
095
095
110
110
125
130
145
140
160
155
175
115
130
125
140
135
155
160
180
190
215
220
255
255
290
285
320
310
350
350
400
395
450
450
510
500
565
Pf = cooling capacity (kW)
qw = water flow (m3/h)
dpw = pressure drop (kPa)
F.L.I. = full load electrical power
F.L.A. = full load operating current
Hp = water pump head pressure
Hu = water pump available pressure
Pf
qw
dpw
[kW]
[m
3
/h]
[kPa]
54
9
17
61
11
21
69
12
26
84
14
17
95
16
21
112
19
15
128
22
20
142
24
17
155
27
20
114
20
23
123
21
26
138
24
32
158
27
24
189
33
34
222
38
28
255
44
24
284
49
29
310
53
33
352
61
24
393
68
30
450
77
23
498
86
28
Ref. Curve
F.L.I.
[kW]
A
2,55
A
2,55
A
2,55
B
3,44
B
3,44
C
4,52
C
4,52
C
4,52
C
4,52
C
4,52
C
4,52
C
4,52
E
8,26
E
8,26
E
8,26
E
8,26
E
8,26
E
8,26
E
8,26
F
10,12
G
11,98
G
11,98
F.L.A.
Hp
[A]
[kPa]
[kPa]
4,7
339
322
4,7
331
310
4,7
323
297
6,4
371
354
6,4
352
332
8,7
351
335
8,7
342
322
8,7
333
316
8,7
325
305
8,7
325
302
8,7
325
299
8,7
325
293
13,6
381
357
13,6
375
341
13,6
367
339
13,6
358
334
13,6
349
320
13,6
339
306
13,6
321
296
17,2
316
286
21,3
346
323
21,3
331
304