7.1.1 Calculation of total minimum water content, total optimal water content and flow rates
Plant side chilled water heat exchanger
CGWF SE
Vopt
[m3]
050
0,45
060
0,51
065
0,57
080
0,69
090
0,78
110
0,93
125
1,07
135
1,17
150
1,28
170
1,45
190
1,64
215
1,85
235
2,04
115
0,95
120
1,01
130
1,14
155
1,33
185
1,57
210
1,81
245
2,11
270
2,33
290
2,52
340
2,92
375
3,21
420
3,63
475
4,10
555
4,78
610
5,27
660
5,69
700
6,00
LEGEND:
Vmin:
minimum water content of the plant
Vopt:
optimal water content of the plant
Q min: minimum water flow to the heat exchanger
Q max: maximum water flow to the heat exchanger
ΔTmax chiller = 10 °C
ΔTmin chiller = 3 °C
dpw = K·Q² / 1000 Q = 0,86 P/ΔT
Page 19
Vmin
K
Q min
[m3]
[m3/h]
0,26
365,3
5,6
0,29
358,0
6,4
0,32
352,4
7,1
0,39
182,4
8,6
0,45
178,5
9,8
0,53
75,6
11,6
0,61
73,8
13,4
0,67
72,7
14,7
0,73
71,7
16,0
0,83
38,5
18,2
0,94
27,1
20,5
1,06
26,6
23,1
1,16
26,2
25,5
0,54
119,4
11,9
0,58
118,5
12,7
0,65
117,0
14,2
0,76
56,4
16,7
0,90
55,3
19,6
1,03
54,5
22,6
1,21
30,8
26,4
1,33
30,5
29,1
1,44
30,3
31,4
1,67
11,6
36,5
1,83
11,4
40,1
2,07
11,2
45,4
2,34
6,3
51,3
2,73
6,1
59,7
3,01
3,6
65,8
3,25
3,6
71,2
3,43
3,6
75,0
Q max
[m3/h]
14,9
16,9
18,9
22,9
26,1
31,0
35,6
39,2
42,6
48,5
54,6
61,6
67,9
31,6
33,7
37,9
44,4
52,3
60,2
70,5
77,5
83,8
97,4
106,9
121,0
136,7
159,2
175,5
189,8
200,0