Installation Sequence Installing The Outdoor Unit; Installation Information - Viessmann Vitocal 200-S Installation And Service Instructions For Contractors

Air/water heat pump, split version for heating and cooling operation
Table of Contents

Advertisement

Installing the outdoor unit

Installation information

Types of installation:
Floorstanding installation with line entry above
ground level
Floorstanding installation with line entry below
ground level
Wall mounting
Technical guide
Floorstanding installation:
Use supports for floorstanding installation (accesso-
ries).
Where such supports cannot be used, install the
external unit freestanding on a solid base of
at least 100 mm height.
In difficult climatic circumstances (temperatures
below zero, snow, humidity) install the appliance on
a plinth of approx. 300 mm height.
Take into account the weight of the external unit: See
the following table.
Wall mounting:
Use the wall mounting bracket set (accessories).
The wall must meet the structural requirements.
Positioning:
Never install with the discharge side facing the main
wind direction.
Provide wall ducts and protective pipes for the refrig-
erant lines and electrical cables without moulded
parts and change of direction.
Weather influences:
Observe wind loads when installing the unit on sites
exposed to the wind.
Incorporate the external unit into the lightning protec-
tion system.
Consider the heat emitted by the unit when planning
your weatherproofing or an enclosure.
Condensate:
Ensure the condensate can drain freely, and create a
permanent gravel bed below the external unit as a
soakaway.
In regions with prolonged cold seasons (e.g. Swe-
den), provide an electric ribbon heater (accessory)
for the condensate pan.
Insulation against structure-borne noise and vibra-
tions between building and external unit:
When line entry is above ground level, fit pipe bends
in the refrigerant lines to isolate vibrations: See
"Connecting refrigerant lines".
Route electrical cables/leads between the internal
and external units free of stress.
Installation only on walls with high weight per area (
2
250 kg/m
), in other words not on lightweight walls,
roof structures etc.
For floorstanding installation, only use the rubber
mounts supplied.
For wall mounting, only use the anti-vibration mounts
from the bracket set.
Never use additional anti-vibration mounts, springs,
rubber mounts, etc.
Weight of outdoor units
Type AWB/AWB-E/
AWB-AC
201.B04
201.B05
201.B07
201.B10
201.B13
201.C10
201.C13
201.C16
Installation sequence
>
Weight in kg
43
66
66
113
113
113
113
121
11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents