Checking The Actuators; Actual Temperatures - Viessmann Vitocal 060-A Installation And Service Instructions For Contractors

Dhw heat pump with dry immersion heater dhw heat pump with connection for external heat generator or solar collectors
Table of Contents

Advertisement

Diagnosis and service checks
Installation menu
(cont.)
Parame-
Delivered condi-
ter
tion
"I3"
OFF
"I4"
OFF
"I5"
OFF
"I6"
OFF

Checking the actuators

Parame-
Delivered condi-
ter
tion
"T1"
0
"T2"
0
"T3"
0
"T4"
0
"T5"
0

Actual temperatures

Connecting the temperature sensors: See page 43.
Parameter
Display range
"t'1"
0 to 99
"t'2"
-20 to 99
34
Setting range
Unit
OFF to 20
min
OFF to 30
Days
OFF or 55 to 65
°C
OFF or ON
Setting range
Unit
0 or 1
0 or 1
0 or 1
0 or 1
0 or 1
Unit
°C
°C
Function
OFF
No photovoltaic system
1 to 20 Signal line for photovoltaic system (multi-
functional relay) is connected (see
page 43).
The set temperature is raised after the mul-
tifunctional relay contact (on site) has been
closed for between 1 and 20 minutes.
Note
The minimum start-up capacity of the multi-
functional relay must be set to 750 W at the
inverter.
OFF
"Increased DHW hygiene" function inactive
1 to 30 "Increased DHW hygiene" function active
The DHW cylinder is automatically heated
to 60 °C at an interval of 1 to 30 days.
Note
Only enable this function if an immersion
heater or external heat generator with con-
trol relay is available.
OFF
Emergency mode not active
55 to 65 Emergency mode active
The set temperature is 55 to 65 °C.
Note
In emergency mode, the DHW is heated
solely by the immersion heater.
Option for the PROGRAM operating program
OFF Standard: DHW heating within the set time
program
ON
NIGHT mode: Optimised DHW heating be-
tween 23:00 h and 05:00 h
The start is delayed in such a manner that the
set DHW temperature is achieved at 05:00 h.
Function at parameter setting "1"
Compressor and fan run for 30 s.
Immersion heater operates for 30 s.
Fan runs for 30 s at speed setting 1 (slow).
Fan runs for 30 s at speed setting 2 (fast).
Only visible if "I1" = 2
Diverter valve for defrosting opens for 30 s.
Information
Bottom cylinder temperature sensor
Air intake temperature sensor