Boiler"/Group 2 - Viessmann Vitodens 222-F Installation And Service Instructions For Contractors

Gas condensing storage combi boiler
Table of Contents

Advertisement

Coding level 2
(cont.)
Coding in the delivered condition
98:1
With LON communication module:
Viessmann system number (in
conjunction with monitoring of sev-
eral systems via Vitocom 300)
99:0
Do not adjust
9A:0
Do not adjust
9b:70
Set flow temperature for external
demand 70 °C
9C:20
With LON communication module:
Monitoring LON subscribers.
If there is no response from a sub-
scriber for 20 min, the values
specified in the control unit are
used. Only then will a fault mes-
sage be issued. (Only for weather-
compensated control units.)
9F:8
Only for heating circuit with mixer:
Differential temperature 8 K (only
for weather-compensated control
units)

"Boiler"/Group 2

Select "Boiler" for weather-compensated control units
(see page 62).
Coding
Coding in the delivered condition
04:1
Minimum burner pause time sub-
ject to the boiler load (specified by
boiler coding card)
06:...
Maximum limit of the boiler water
temperature, defaulted by the boil-
er coding card in °C
0d:0
Do not adjust
0E:0
Do not adjust
13:1
Do not adjust
14:1
Do not adjust
15:1
Do not adjust
21:0
No service interval (hours run) se-
lected.
23:0
No time set for burner service in-
terval
24:0
No "Service" indication on the dis-
play
Possible change
98:1
System number adjustable from 1 to
to
5
98:5
9b:0
Set value adjustable from 0 to
to
127 °C (limited by boiler-specific pa-
9b:127
rameters)
9C:0
No monitoring
9C:5
Time adjustable from 5 to 60 min
to
9C:60
9F:0
Differential temperature adjustable
to
from 0 to 40 K
9F:40
Select "2" for constant temperature control unit (see
page 62).
Possible change
04:0
Systems with low loss header:
Pause time set permanently (speci-
fied by boiler coding card)
06:20
Maximum limit adjustable within the
to
ranges specified by the boiler
06:127
21:1
The number of hours run before the
to
burner should be serviced is adjust-
21:100
able from 100 to 10 000 h.
One adjusting step
23:1
Interval adjustable from 1 to
to
24 months
23:24
24:1
"Service" is shown on the display
(address is automatically set and
must be manually reset after a serv-
ice has been carried out)
Codes
100 h
67