Commissioning, inspection, maintenance
Further details regarding the individual steps
Checking the water quality
Enter the amount of top-up water, the water hardness and the pH value in the
tables.
For water quality requirements, see page 75.
Meter read-
Fill and top-
ing
up water
3
3
m
m
The pH value should be between 8.2 and 9.5.
Checking the expansion vessel and system pressure
Note
Please observe expansion vessel man-
ufacturer's instructions.
Carry out this test on a cold system.
36
Total water
volume
Feedwater Boiler wa-
°dH
3
m
1. Drain the system until the pressure
(cont.)
Total hardness
ter
°dH
gauge indicates "0" or close the cap
valve on the expansion vessel and
reduce the pressure in the expansion
vessel.
pH value Date