Checking the water quality
Enter the amount of top-up water and the total hard-
ness of the feed and boiler water into the following
table.
For water quality requirements, see page 28.
Meter reading
Fill and top-up water
m
3
m
3
The total hardness of the feed and top-up water must
not exceed the standard values specified by VDI 2035
(see page 28).
Cleaning and reconnecting the condensate drain system
The condensate drain system comprises the conden-
sate drain, siphon, neutralising system and all hoses
and pipes running between them.
Commissioning, inspection, maintenance
Total water volume
Feedwater
m
3
The pH value should be between 8.2 and 9.5.
Note
Clean the inside of the condensate drain system at
least annually.
Total hardness
pH value
Boiler water
Date