Commissioning, inspection, maintenance
Further details regarding the individual steps
Checking the gas type
1. Check the gas type and Wobbe index
(Wo) with your gas supply utility.
■ With the natural gas E setting, the
boiler can be operated in the
Wobbe index range 12.0 to
3
16.1 kWh/m
■ The natural gas LL setting ena-
bles boilers to be operated in the
Wobbe index range 10.0 to
13.1 kWh/m
3
(not in a and c).
■ With the LPG P setting, the boiler
can be operated in the Wobbe
index range 20.3 to 21.3 kWh/m
(72.9 to 76.8 MJ/m
Converting to natural gas LL
(not in a and c)
B C D
F
A
01. Close the gas shut-off valve.
10
(43.2 to 58.0 MJ/m
(36.0 to 47.2 MJ/m
3
).
E G
2. In the delivered condition, the burner
is set up for natural gas E. If required,
convert the burner to a different gas
type in accordance with details provi-
ded by your gas supply utility (see
from page 10).
3
).
3. Record the gas type in the report (on
page 74).
3
)
3
02. Switch OFF the ON/OFF switch on
the control unit.
03. Switch OFF the mains isolator (out-
side the installation room) or isolate
the mains power and secure against
unintentional reconnection.
04. Undo fitting A from the gas supply
pipe.
05. Pull compensation hose G from
the gas train.
06. Release the gas train from flange
E.
07. Remove restrictor C with rubber
cork gasket D.
(cont.)