Checking the condensate drain and the neutralising system (if
installed)
Add water to the combustion chamber.
Note
The water must flow from the conden-
sate drain pipe without back pressure.
If necessary, clean the condensate drain
pipe again.

Checking the burner gauze assembly

Danger
Escaping gas leads to a risk of
explosion.
Close the gas shut-off valve.
B
A
1. Undo fitting A from the gas supply
pipe.
2. Undo the screws on the boiler door
and open the door.
Commissioning, inspection, maintenance
3. Check the metal gauze of burner
gauze assembly B for damage.
4. Replace burner gauze assembly B
if required.
Danger
Touching hot components can
cause burns.
Only perform work on the burner
when it has cooled down.
!
Please note
Scratches inside the combustion
chamber can lead to corrosion.
Never put tools or other objects
into the combustion chamber.
(cont.)