GALAXY II
If the burner does not fire, please check the following:
Is controlled getting a call for heat? Decimal light on display will illuminate. If decimal
is not lit, check thermostat setting and wiring.
Is red indicating light on? Control is on able to sence water.
• Confirm water level in boiler.
• Remove and check sensor to ensure metal to metal contact between sensor and
inside surface of well.
Has the vent damper open? Control will not fire burn if damper did not fully open.
• Check the Molex plugs on both the control end and the damper end.
• Check to be sure the vent damper motor turns.
• Verify the vent damper and switch has closed.
Call Slant/Fin Tech Support: Experts at Slant/Fin are ready to help.
Call us at (800) 873-4346