8: Annunciators; Ann-Bus Setup - Honeywell NOTIFIER NFW-50X Manual

Addressable fire alarm control panel
Hide thumbs Also See for NOTIFIER NFW-50X:
Table of Contents

Advertisement

Programming
3.6.8 Annunciators
PROGRAMMING
1=HISTORY
2=COMMUNICATOR
3=ANNUNCIATORS
Programming Screen #3
A printer module, graphic annunciator module, LCD annunciator module, LED annunciator module, and relay module can be pro-
grammed into the NFW-50X system. These devices communicate with the FACP over the ANN-BUS terminals on the control panel.

ANN-BUS Setup

ANN-BUS SELECT
1=PRIMARY
2=SECONDARY
3=ANN-BUS OPTIONS
Annunciators Screen
ANN-BUS Enabled
The ANN-BUS must be enabled if any modules are connected to the ANN-BUS terminals. To enable the ANN-BUS, press 1 while
viewing ANN-BUS screen #1 so that the display reads ANN (XXX) Enabled Yes. Each press of the 1 key will cause the display to toggle
between ANN (XXX) Enabled Yes and ANN (XXX) Enabled No.
Modules Installed
ANN XXX
1=ENABLED
2=MODULES INSTALLED
3=AUTO-CONFIGURE
ANN-BUS (XXX) Screen #1
Pressing the down arrow key will allow the programmer to view additional screens displaying Addresses 1-8. To select one or more
addresses for the installed module(s), press the number key corresponding to the module address in each screen. The following screen
will be displayed for each address:
Pressing 1 for Type will display the following screens:
ANN-BUS MODULE TYPE
1=NOT INSTALLED
2=ANN-80 MODULE
3=ANN-100 MODULE
Module Type Screen #1
Press the number corresponding to the module/device type that is installed with the selected address.
NOTE: If the module type selected is the ANN-80, ANN-100, or ANN-S/PG, or if Not Installed is selected, the ANN-BUS Address Screen
shown on the previous page will be displayed following the module selection. The options selected for each of these modules will be the
same for all modules of the same type (refer to "ANN-S/PG (Print) Options" on page 94 and "ANN-80/100 Options" on page 94).
If ANN-I/O, ANN-LED, or ANN-RLY is the selected module type, the following ANN-BUS Address Screen will be displayed:
86
Pressing 3 while viewing Programming Screen #3 will cause the control panel to display the following
screens:
1=PRIMARY
2=SECONDARY
3=ANN-BUS OPTIONS
Two ANN-BUS circuits are available on the NFW-50X. Press 1 to configure the Primary ANN-BUS or
press 2 to configure the Secondary ANN-BUS. The following screens will be displayed for either ANN-
BUS circuit where (XXX) indicates either Primary or Secondary..
ANN XXX
1=ENABLED
2=MODULES INSTALLED
3=AUTO-CONFIGURE
ANN-BUS Screen #1
If an ANN-BUS module is installed, press 2 for Modules Installed to select ANN-BUS addresses for the
NO
module(s). The only difference between the two programming screens are the addresses. The Primary Bus
module addresses will have a prefix of "1-" while the Secondary Bus module addresses will have a prefix
of "2-". The following screen will be displayed for either bus circuit.
1=ADDR. X-1
2=ADDR. X-2
3=ADDR. X-3
ANN-BUS Modules Screen #1
ANN-BUS ADDRESS
1=TYPE
ANN-BUS ADDRESS
1=TYPE
2=MODULE OPTIONS
ANN-BUS SELECT
NO
ANN-BUS MODULES
NONE
NONE
NONE
ANN-BUS MODULE X-1
NONE
ANN-BUS Address Screen
ANN-BUS MODULE TYPE
1=ANN-I/O MODULE
2=ANN-S/PG MODULE
3=ANN-LED MODULE
Module Type Screen #2
ANN-BUS MODULE X-1
ANN-I/O
ANN-BUS Address Screen
NFW-50X Manual — P/N LS10129-001NF-E:C 7/25/2018
Master Programming Level
ANN XXX
1=CLASS A
NO
ANN-BUS Screen #2
ANN-BUS MODULE TYPE
1=ANN-RLY MODULE
Module Type Screen #3