Programming
Pre-signal
EDIT MONITOR
1=PRE-SIGNAL
WIRELESS
NO
Edit Monitor Screen #3
Wireless
EDIT MONITOR
1=PRE-SIGNAL
WIRELESS
Edit Monitor Screen #3
Walktest
EDIT MONITOR
1=WALKTEST
2=ZONE ASSIGNMENT
000    
Edit Monitor Screen #4
Zone Assignment
A maximum of five zones can be programmed to each addressable monitor module. Pressing 2 while viewing Edit Monitor Screen #4
displays the following screen:
Note that Z*** represents the Zone Number(s) corresponding to this device. The factory default for an unprogrammed device is Z000 for
general alarm zone. A flashing cursor will appear on the first 0 to the left. Enter the three digit number corresponding to the zone that is
to be assigned to this device. The cursor moves to the next Z*** designation. Continue entering zone assignments or the remaining zones
can be left blank or programmed as general alarm zones Z00. When all desired changes have been made, press the Enter key to store the
zone assignments. The display will return to the Edit Monitor Screen #4.
Noun/Adjective
EDIT MONITOR
1=NOUN/ADJECTIVE
2=DESCRIPTION

Edit Monitor Screen #5
1=STANDARD ADJECTIVE
2=STANDARD NOUN
3=CUSTOM ADJECTIVE
4=CUSTOM NOUN
Noun/Adjective Screen

1=NORTH
2=SOUTH
3=EAST
Adjective Screen #1

1=3RD
2=4TH
3=5TH
Adjective Screen #5
60
To enable the Pre-signal feature, press 1 while viewing Edit Monitor Screen #3 until the display reads Pre-
NO
signal Yes. Each press of the 1 key will cause the display to toggle between Pre-signal Yes and Pre-signal
No. Refer to"Presignal" on page 108 for additional information.
The Wireless selection will update automatically if the system recognizes a wireless device. If the module is
NO
wireless, the display reads Wireless Yes. If the module is wired, the display will read Wireless No. Fore more
NO
information on the SWIFT wireless network, refer to the SWIFT manual, #LS10036-000NF-E.
The Walktest feature allows one person to test the system devices without the necessity of manually reset-
ting the control panel after each device activation. To enable devices, which are connected to a monitor
module, for the Walktest feature, press 1 while viewing the Edit Monitor Screen #4 until the display reads
Walktest Yes. Each press of the 1 key will cause the display to toggle between Walktest Yes and Walktest No.
Refer to "Walktest" on page 109 for additional information.
The Noun/Adjective selection allows the programmer to enter specific descriptors about the monitor mod-
ule currently being programmed. Pressing 1 while viewing Edit Monitor Screen #5 will cause the following
screen to be displayed:
Pressing 1 while viewing the Noun/Adjective Screen will cause the following screen(s) to be displayed.
Note that the keyboard down arrow key must be pressed to see all the Adjective screens. Press the number
corresponding to the adjective that is to be used as a descriptor for the location of the monitor module cur-
rently being programmed.

1=WEST
2=FRONT
3=CENTER
Adjective Screen #2

1=FLOOR 1
2=FLOOR 2
3=FLOOR 3
Adjective Screen #6
ZONE ASSIGNMENT
Z000ZZZZ
Zone Assignment Screen
1=STANDARD ADJECTIVE
2=STANDARD NOUN
3=CUSTOM ADJECTIVE
4=CUSTOM NOUN
Noun/Adjective Screen

1=REAR
2=UPPER
3=LOWER
Adjective Screen #3

1=FLOOR 4
2=FLOOR 5
3=ROOM
Adjective Screen #7
NFW-50X Manual — P/N LS10129-001NF-E:C 7/25/2018
Master Programming Level

1=MAIN
2=FIRST