Master Programming Level
Monitor module type selection will affect the function of the point as follows:
Pull-Station
User-Defined-1
Waterflow
User-Defined-2
Monitor
User-Defined-3
Future
Future
Smoke-Conventional
User-Defined-5
Heat Conventional
User-Defined-6
Medic Alert
User-Defined-7
Hazard Alert
User-Defined-8
Tornado Alert
User-Defined-9
Phone
User-Defined-10
Tamper
User-Defined-11
Supervisory
User-Defined-12
Supervisory AR
User-Defined-13
HVAC OVRRIDE
Power Monitor
User-Defined-14
Trouble Monitor
User-Defined-15
Process Monitor
User-Defined 16
Process Monitor AR
User-Defined-17
Future
Future
Ack Switch
Sil Switch
Reset Switch
Drill Switch
PAS Bypass
HVAC RESTART
Drill Switch AR
Wireless Gateway
1 Combination systems employing these non-fire monitor types require the SLC loop to be programmed
by the installer for Class B operation and isolator modules must be employed on each non-fire branch
of the SLC as shown in the SLC Wiring Manual (document number 52304 and 515253). Fire and non-
fire devices must not be used on the same SLC branch. For UL2017 compliance, The N-ANN-LED
annunciator must be used to indicate the active, dedicated zone or device
2 For entries ending in AR, AR refers to AutoResettable.
3 For HVAC RESTART and HVAC OVRRIDE descriptions, refer to "Monitor Module Operation" on
page 141.
NFW-50X Manual — P/N LS10129-001NF-E:C 7/25/2018
Monitor Type
Fire Alarm
same as previous (Pull-Station)
Fire Alarm Delayed
same as previous (Waterflow)
Fire Alarm
same as previous (Monitor)
not used
not used
Fire Alarm
same as previous (Smoke-Conventional)
Fire Alarm
same as previous (Heat-Detector)
1
General Purpose Signaling, latching
same as previous (Medic-Alert)
1
General Purpose Signaling, latching
same as previous (Hazard-Alert)
1
General Purpose Signaling, latching
same as previous (Tornado-Alert)
Active Phone (LCD display only)
same as previous (Phone)
Supervisory, nonlatching (tracking)
same as previous (Tamper)
Supervisory, latching
same as previous (Supervisory)
2
Supervisory, nonlatching (tracking)
same as previous (Supervisory-AR)
3
Switch Supervisory, nonlatching (tracking)
Power Fault
same as previous (Power Monitor)
Trouble
same as previous (Trouble Monitor)
General Purpose Signaling, latching
1
same as previous (Process-Monitor)
1,2
General Purpose Signaling, nonlatching (tracking)
same as previous (Process-Monitor-AR)
not used
not used
Acts like panel Acknowledge Key
Acts like panel Silence Key
Acts like panel Reset Key
Acts like panel Drill Key
PAS Disable
3
Switch (see note 2)
2
Acts like panel Drill Key, non-latching (tracking)
SWIFT gateway needs this type to display wireless troubles at the FACP
Action When Activated
Table 3.1 Monitor Types
Programming