Unit Dimensions - York SUNLINE PLUS D1EG090 Installation Instruction

Gas / electric single package air conditioners
Table of Contents

Advertisement

33-7/8
(090)
39-7/8
(120)
47-7/8
(150)
DUCT COVERS - Units are shipped with all air duct
openings covered.
For side duct applications;
1. Remove and discard the supply and return air duct
covers.
2. Connect ductwork to duct flanges on the rear of the
unit.
For bottom duct applications;
1. Remove the side supply and return air duct covers to
gain access to the bottom supply and return air duct
covers.
2. Remove and discard the bottom duct covers.
3. Replace the side duct covers.
DETAIL "X"
(SIDE SUPPLY AND RETURN AIR OPENINGS)
FIG. 10 - UNIT DIMENSIONS (7-1/2 - 12-1/2 TON)
Unitary Products Group
CONDENSER
COIL
All dimensions are in inches. They are sub-
ject to change without notice. Certified di-
mensions will be provided upon request.
HOLE
A
B
C
D
*
Openings in the bottom of the unit can be located by the slice in the
insulation.
Front
Back
Left Side (Filter Access)
Right Side (Cond. Coil)
1
Below Unit
2
Above Unit
1
Locate unit so that the vent air outlet hood is at least:
• Three (3) feet above any forced air inlet located within 10 horizontal feet (excluding
those integral to the unit).
• Four (4) feet below, 4 horizontal feet from, or 1 foot above any door or gravity air inlet
into the building.
• Four (4) feet from electric meters, gas meters, regulators and relief equipment.
2
Units may be installed on combustible floors made from wood or class A, B or C
roof covering material.
3
Units must be installed outdoors. Overhanging structures or shrubs should not
obstruct the condenser air discharge outlet.
NOTE: A 1" clearance must be provided between any combustible material and the
supply air ductwork for a distance of 3 feet from the unit.
The products of combustion must not be allowed to accumulate within a confined
space and recirculate.
RETURN AIR
SUPPLY AIR
CONDENSER AIR
OUTDOOR AIR
(Economizer)
UTILITIES ENTRY DATA
OPENING
SIZE
USED FOR
(DIA.)
3/4" KO
Control
Wiring
7/8" KO
Power Wiring
2" KO
(Side or Bottom)*
2" KO
Gas Piping (Front)
1-11/16" KO
Gas Piping (Bottom)*
CLEARANCES
24"
12" (Less Economizer)
36" (With Economizer)
24" (Less Economizer)
54" (With Economizer)
24"
20"
72" with 36" maximum
Horizontal Overhang
(For Condenser Air Discharge)
530.22-N4Y
Side
Bottom*
9