Error code
Remote control:
E11
1. Applicable model
All models
2. Error detection method
Indoor unit address has been set
using the "Indoor unit address
set" function of remote control.
3. Condition of error displayed
Same as above
4. Presumable cause
Wrong address setting method.
(It cannot set addresses from the
remote control.)
Note:
LED
Green
Red
Indoor
Keeps flashing Keeps flashing
5. Troubleshooting
Diagnosis
E11 occurs
Is "Indoor unit
address set" function of remote
control used?
In case the wiring is below and "Indoor unit address
set" is used, E11 is appeared.
IU
IU
R/C
181
-
Content
Address setting error of
indoor units
YES
IU
-
'16 • PAC-T-240
Countermeasure
Change of address setting
method. Addresses are
set using the dip switch
(SW2) on the indoor
control PCB. (Refer to
the page 120.)