Indoor Fan Motor Anomaly - Mitsubishi Heavy Industries FDT100VNP1VF2 Technical Manual

Standard inverter packaged air-conditioners
Table of Contents

Advertisement

Error code
E16
Remote control:
Note(1) Value in ( ) is for the FDU, FDUM series FMI2 only.
1. Applicable model
All models
2. Error detection method
Detected by rotation speed of
indoor fan motor
3. Condition of error displayed
When actual rotation speed of
indoor fan motor drops to lower
-1
than 200min
for 30 seconds
continuously, the compressor
and the indoor fan motor
stop. After 2-seconds, it starts
again automatically, but if this
error occurs 4 times within
60 minutes after the initial
detection.
4. Presumable cause
• Defective indoor power PCB
• Foreign material at rotational
area of fan propeller
• Defective fan motor
• Dust on control PCB
• Blown fuse
• External noise, surge
Note:
LED
Green
Red
Keeps flashing 1(2)-time flash
Indoor
5. Troubleshooting
Diagnosis
Does any
foreign material
intervene in rotational area
of fan propeller?
NO
Does the fan
rotate smoothly when turned
by hand?
YES
(1)
Is DC280V
detected between �-� of
fan motor connector
CNM?
YES
(FDF: F202, F203) blown?
Power source reset
Is it normalized?
182
-
Content

Indoor fan motor anomaly

YES
NO
Note (1) � for GND
NO
Is the fuse F3 or F4
NO
YES
NO
YES
-
'16 • PAC-T-240
Countermeasure
Remove foreign material.
Replace the fan motor.
Check power voltage.
Replace faulty fan motor
and power PCB.
Replace fan motor. (If the
error persists after replacing
the fan motor, replace the
indoor control PCB.)
Malfunction by temporary
noise