E5 Communication Error During Operation - Mitsubishi Heavy Industries FDT100VNP1VF2 Technical Manual

Standard inverter packaged air-conditioners
Table of Contents

Advertisement

Error code
E5
Remote control:
1. Applicable model
All models
2. Error detection method
When normal communication
between indoor and outdoor
unit is interrupted for more than
2 minutes.
3. Condition of error displayed
Same as above is detected
during operation.
4. Presumable cause
• Unit No. setting error
• Broken remote control wire
• Faulty remote control wire
connection
• Faulty outdoor control PCB
Note:
LED
Green
Red
Keeps flashing 2-time flash
Indoor
5. Troubleshooting
Diagnosis
Note (1) Inspect faulty connections (disconnection,
looseness) on the outdoor unit terminal block.
Is the
connection of signal
wires at the outdoor unit
side OK?
YES
Note (2) Check for faulty connection or breakage of
Is the
signal wires between indoor-outdoor units.
connection of signal
wires between indoor-outdoor
units OK?
YES
Power source reset
Has the remote
control LCD returned to
normal state?
175
-
Content
Communication error during operation
NO
NO
NO
YES
-
'16 • PAC-T-240
Countermeasure
Repair signal wires.
Repair signal wires.
Defective outdoor control
PCB (Defective network
communication circuit) ➞
Replace.
Unit is normal.
(Malfunction by temporary
noise, etc.)