E6 Indoor Heat Exchanger Temperature Thermistor Anomaly - Mitsubishi Heavy Industries FDT100VNP1VF2 Technical Manual

Standard inverter packaged air-conditioners
Table of Contents

Advertisement

Error code
E6
Remote control:
1. Applicable model
All models
2. Error detection method
Anomalously low temperature
or high temperature (resistance)
is detected on the indoor heat
exchanger thermistor (Thi-R1,
R2 or R3).
3. Condition of error displayed
• When the temperature
thermistor detects -50°C
or lower for 5 seconds
continuously, the compressor
stops. After 3-minutes delay,
the compressor starts again
automatically, but if this
error occurs again within
60 minutes after the initial
detection.
• Or if 70°C or higher is
detected for 5 seconds
continuously.
4. Presumable cause
• Defective indoor heat
exchanger thermistor
connector
• Indoor heat exchanger
temperature thermistor
anomaly
• Faulty indoor control PCB
Note:
LED
Green
Red
Keeps flashing 1-time flash
Indoor
5. Troubleshooting
Diagnosis
Is the
connection of indoor heat
exchanger temperature thermistor
connector OK?
YES
Are
characteristics of indoor
heat exchanger temperature
thermistor OK?
Temperature-resistance characteristic
(Broken wire)
15
10
5
(Short circuit)
0
10
Temperature (°C)
176
-
Content
Indoor heat exchanger
temperature thermistor anomaly
NO
NO
YES
°C
5kΩ at 25
20
30
40
50
-
'16 • PAC-T-240
Countermeasure
Correct. ➞ Insert connector
securely.
Defective indoor heat
exchanger temperature
thermistor ➞ Replace.
Defective indoor control
PCB ➞ Replace.
(Defective indoor unit heat
exchanger temperature
thermistor input circuit)