Indoor Heat Exchanger Temperature Thermistor Anomaly; Condition Of Error Displayed -26; When The Temperature Thermistor Detects -50; C Or Lower For 5 Seconds -22 - Mitsubishi Heavy Industries FDC112KXEN6 Technical Manual

Table of Contents

Advertisement

Error code
Remote controller:
E6
7-segment display:
1. Applicable model
All models
2. Error detection method
Anomalously low temperature
or high temperature (resistance)
is detected by the indoor heat
exchanger thermistor (Thi-R1,
R2 or R3).
3. Condition of error displayed
• When the temperature
thermistor detects -50°
C or lower for 5 seconds
continuously, the compressor
stops. After 3-minutes delay,
the compressor starts again

automatically, but if this

anomaly occurs again within

60 minutes after the initial
detection.
• Or if 70°C or higher is
detected for 5 seconds
continuously.
4. Presumable cause
• Defective indoor heat
exchanger thermistor
connector
• Defective indoor heat
exchanger thermistor
• Faulty indoor control PCB
Note:
LED
Green
Red
Keeps flashing 1 time flash
Indoor
Keeps flashing Stays Off
Outdoor
5. Troubleshooting
Diagnosis
Is the
connection of indoor heat
exchanger temperature thermistor
connector OK?
YES
Are the
characteristics of indoor
heat exchanger temperature
thermistor OK?
Temperature-resistance characteristic
15
10
5
0
10
Temperature (°C)
334
Content
Indoor heat exchanger
temperature thermistor anomaly
NO
NO
YES
°C
5kΩ at 25
20
30
40
50
°C
Note (1) 22.5kΩ at -6
Countermeasure
Correct.  Connect
connector.
Defective indoor heat
exchanger temperature
thermistor  Replace.
Defective indoor control
PCB  Replace.
(Defective indoor heat
exchanger temperature
thermistor input circuit)