Fitting The Cover; Connections On The Heating Water Side - Viessmann VITOCELL 300-V VIB-A+ Installation And Service Instructions Manual

Dhw cylinder with internal indirect coil
Hide thumbs Also See for VITOCELL 300-V VIB-A+:
Table of Contents

Advertisement

Installation sequence
500 l capacity
(cont.)

Fitting the cover

A
2.
Fig. 13
Cap with Viessmann logo
A

Connections on the heating water side

Connect all pipework with detachable fittings.
Seal any connections that are not required with red
brass caps.
Adjust the temperature controller and high limit
safety cut-out so that the DHW temperature in the
DHW cylinder does not exceed 95 °C.
!
Please note
The internal indirect coil is installed with gas-
kets.
Temperatures > 150 °C at the connections will
damage the gaskets.
Maintain a safe distance when soldering and
welding.
Realigning the connector will damage the gas-
kets.
Permissible heating water flow temperature
Heating water side
Permissible operating pressure
Heating water side
DHW side
Test pressure
Heating water side
DHW side
Permissible DHW temperature
16
1.
Note
The soft side of the thermal insulation must rest
against the cylinder body.
160 °C
10 bar
1 MPa
10 bar
1 MPa
16 bar
1.6 MPa
16 bar
1.6 MPa
95 °C