Location; Vent Termination Clearances - Superior Fireplaces DRT6300 Series Installation And Operation Instructions Manual

Power-vent direct-vent gas fireplaces
Table of Contents

Advertisement

INNOVATIVE HEARTH PRODUCTS • POWER VENT DV GAS FIREPLACES (DRT6340TYN AND DRT6345TYN) • INSTALLATION INSTRUCTIONS

LOCATION

In selecting the location, the aesthetic and
functional use of the appliance are primary
concerns. However, vent system routing to
the exterior and access to the fuel supply are
also important.
Due to high temperatures, the appliance
should be located out of traffic and away from
furniture and draperies (Figure 2).
En raison des températures élevées,
l'appareil devrait être installé dans un
endroit où il y a peu de circulation et loin
du mobilier et des tentures (Figure 2).
The location should also be free of electrical,
plumbing or other heating/air conditioning
ducting.
Be aware that this is a heat producing ap-
pliance. Objects placed above the unit are
exposed to elevated temperatures.
Do not insulate the space between the appli-
f i r e - p a r t s . c o m
ance and the area above it.
The appliance must be mounted on a fully
supported base extending the full width and
depth of the unit. The appliance may be lo-
cated on or near conventional construction
materials. However, if installed on combustible
materials, such as carpeting, vinyl tile, or other
combustible material other than wood flooring,
the appliance shall be installed on a metal or
wood panel extending the full width and depth
of the appliance.
8
Room Divider
Application
Recessed
Application
Figure 2 - Typical Installation

VENT TERMINATION CLEARANCES

These instructions should be used as a guideline and do not supersede local codes in any way.
Install venting according to local codes, these instructions, and the current (USA) National Fuel
Gas Code ANSI-Z223.1 / NFPA 54, or (Canada) CAN/CGA-B149.1 standards.
Horizontal Vent Termination Clearances
The horizontal vent termination must have a minimum of 3" (77 mm) clearance to any overhead
combustible projection of 2-1/2" (64 mm) or less (see Figure 3). For projections exceeding 2-1/2"
(64 mm), see Figure 3. For additional vent location restrictions refer to Figure 4 on Page 9.
See Figure 19 on Page 19 for the re-
cess allowances, into exterior walls,
of the power vent terminations.
Side Elevation View
Figure 3 - Horizontal Vent Termination Clearances
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
NOTE: When the unit is installed with
one side flush with a wall, the wall on
the other side of the unit must not extend
beyond the front edge of the unit.
Drywall
Horizontal
Termination
Fireplace
Top of Fireplace
Opening
Combustible Projection
2-1/2" or less in length
Combustible Projection
Greater than 2-1/2" in length
Ventilated or
Unventilated Soffit
(77 mm)
24"
(610 mm)
Power Vent Termination
(457 mm)
Combustible
Noncombustible
3".
18"