Connect the wiring and power up

Figure 5-1: Transmitter Wiring Diagrams (4–20 mA)
A. 24 Vdc supply
B. R
≥ 250
L
C. Current meter (optional)
Shielded twisted pair cable should be used for best results. Use 24 AWG or
larger wire that does not exceed 5,000 ft. (1500 m) in length. If applicable,
install wiring with a drip loop. Arrange the drip loop so the bottom is lower
than the conduit connections and the transmitter housing.