Installation
Should several units be connected
to the same condensate drain line,
respect line design conditions as
indicated in Figure 18.
As an option, units can be supplied
with a factory-mounted condensate
pump. The pump is fitted directly on
the condensate tray and can afford
a maximum manometric height of
6m (See Figure 15).
Figure 15 - Condensate pump option for on/off control - general purpose (GP) control
4
5
1 = Condensate tray
2 = Condensate pump
3 = Condensate pump suction
4 = Vent
5 = Condensate pump discharge
6 =Towards condensate evacuation
The condensate pump is equipped
with a floating sensor which will
stop chilled water flow as soon as
the alarm level is reached, while
continuing to evacuate condensate
water.
It is recommended to secure
connection between the tube and
the drain with a clamp or a collar.