4.2. Check Equipment

Inspect equipment. File a claim with shipping company prior to
installation if shipment is damaged or incomplete.

4.3. Location

ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or death.
Disconnect power before routing control wiring.
All wiring must comply with national, state, and local codes.

4.3.1. Wall Control

The Evolution Connex Control is the command center for the Evolution
System. It should be located where it is easily accessible and visible to
the adult homeowner or end user. For accurate temperature measurement,
the following guidelines should be followed:
The Evolution Connex Control, Remote Room Sensors and Smart
Sensors SHOULD be mounted:
• Approximately 5-ft (1.5 m) from the floor.
• Close to or in a frequently used room, preferably on an inside
partitioning wall.
• On a section of wall without pipes or ductwork.
The Evolution Connex Control and Sensors SHOULD NOT be
mounted:
• Close to a window, on an outside wall, or next to a door leading to the
outside.
• Exposed to direct light or heat from a lamp, sun, fireplace, or other
temperature-radiating objects which could cause a false reading.
WARNING
!
12