Freeze Limits; Lockout Count - Bryant Evolution Connex Control Installation Instructions Manual

Hide thumbs Also See for Evolution Connex Control:
Table of Contents

Advertisement

A160188b

6.3.7.1. Freeze Limits

This setting controls the temperature level to which the loop liquid can drop before the Geo HP
unit will stop operating. See the Geo HP Installation Instructions for more details. Typically,
26°F is chosen for open-loop systems using untreated water; and 15°F is chosen for closed-loop
systems using glycol or other anti-freeze solutions. After the selection is made, touch SAVE.
• Freeze Limits: 26°F or 15°F. Default = 26°F
A150179

6.3.7.2. Lockout Count

This setting controls the number of times within an hour that the HPS or LPS trips before the
Geo HP compressor will lockout for four hours. After the selection is made, touch SAVE.
• Lockout Count: 4 or 2
• Default = 2
35