17.4.17 H98 (Error Code Stored in Memory and no alarm is triggered / no TIMER LED
flashing)
Malfunction Decision Conditions
Indoor high pressure is detected when indoor heat exchanger is detecting very high temperature when the unit is
operating in heating operation.
Phenomena: unit is stopping and re-starting very often in heating mode
Malfunction Caused
Indoor heat exchanger thermistor
Clogged air filter or heat exchanger
Over-bent pipe (liquid side)
Troubleshooting
When abnormality indication starts again
Check the indoor unit intake air filter
Is the air filter dirty?
Check the dust accumulation on the indoor unit heat exchanger
Is the indoor unit heat exchanger dirty?
Check the indoor pipe temperature thermistor:
Plug out connector (CN-TH) from the indoor unit PCB
Measure the resistance of the indoor heat exchanger
temperature thermistor
Is the measured resistance of the indoor pipe temperature
thermistor matches the value specified in its characteristic
chart?
NO
NO
YES
Caution
YES
Clean the air filter
YES
Clean the indoor unit heat exchanger
Defect in indoor pipe temperature
NO
thermistor
Replace the indoor pipe temperature
thermistor
Check the piping & installation condition
Replace piping / reinstall the unit
if necessary
113
For safety reason and to prevent
component breakdown, always switch
off the power before remove and
connect the component.