Panasonic CS-25XKE Service Manual page 104

Table of Contents

Advertisement

17.4.8
H27 (Outdoor Air Temperature Sensor Abnormality)
Malfunction Decision Conditions
During startup and operation of cooling and heating, the temperatures detected by the outdoor air temperature
sensor are used to determine sensor errors.
Malfunction Caused
Faulty connector connection.
Faulty sensor.
Faulty PCB.
Troubleshooting
When abnormality indication starts again
Check the connector connection:
Turn off the power
Check the connector connection
Is the connector connection normal?
Check the outdoor air temperature sensor:
Plug out connector from the outdoor unit PCB
Measure the resistance of the outdoor air temperature
sensor
Is the measured resistance of the outdoor air temperature
sensor matches the value specified in its characteristic
chart?
Sensor (Thermistor)
Characteristics
70
1 Outdoor Air Sensor
2 Outdoor Heat Exchanger
60
Sensor
50
40
1
30
2
20
10
0
-10
0
10
Temperature (ºC)
YES
YES
20
30
40
50
For safety reason and to prevent component
breakdown, always switch off the power
Caution
before remove and connect the component.
NO
Connector poor contact
Correct the connection
NO
Defect in outdoor air temperature sensor
Replace the outdoor air temperature sensor
Defect in outdoor unit PCB
Replace the outdoor unit PCB
104