Installing The Vent Pipe Adapter And Combustion Air Pipe Adapter; Vent Coupling And Adapter With Gaskets - Carrier 59SC5B Installation, Start-Up, Operating And Service And Maintenance Instructions

Single stage, 4-way multipoise, 35-in. (889 mm) condensing gas furnace
Hide thumbs Also See for 59SC5B:
Table of Contents

Advertisement

Installing the Vent Pipe Adapter and Combustion Air
Pipe Adapter
WARNING
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal
injury or death.
To route the vent pipe and combustion air pipe through the
furnace, the manufacturer supplied kit must be used. Failure
to properly seal the blower compartment from the furnace
vestibule could result in the circulation of carbon monoxide
throughout the structure. The vent pipe and combustion air
pipe must be a continuous pipe while passing through the
blower compartment. Seals supplied in this kit must be
installed per the instructions provided. Follow all
procedures outlined in these instructions.
WARNING
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury
or death.
DO NOT use cement to join polypropylene venting systems.
Follow the polypropylene venting system manufacturer's
instructions for installing polypropylene venting systems.
Attach gaskets to vent pipe and
combustion air adapters.
Fig. 43 - - Vent Coupling and Adapter with Gaskets
47
NOTE: The rubber coupling that attaches to the vent pipe adapter
must be used. The adapter seals the vent pipe to the casing and
reduces the strain on the vent elbow attached to the inducer.
1. Apply the gaskets to the vent pipe and combustion air pipe
adapters. If supplied, remove and discard round center
"slug" from interior of gasket. See Fig. 43.
NOTE: The vent pipe adapter can be distinguished from the inlet
pipe adapter by the absence of an internal pipe- -stopping ring. The
vent pipe can pass through the vent pipe adapter; it cannot pass
through the inlet pipe adapter.
2. Align the screw holes in the plastic vent pipe adapter with
the dimples in the casing.
3. Pilot drill the screw holes for the adapter in the casing and
attach the vent pipe adapter to the furnace with sheet metal
screws
4. Slide the end of the rubber vent coupling with notches in it
over the standoffs on the vent pipe adapter.
5. Insert a length of vent pipe through the coupling into the
outlet of the vent elbow.
6. Tighten the clamp around the outlet of the vent elbow.
Torque the clamp to 15 lb- -in.
Vent Coupling and Adapter
A13074

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents