Example Of Field Drain Attachment; To Relocate The Condensate Trap - Carrier 59SC2D Installation, Start-Up, Operating And Service And Maintenance Instructions

Single stage, 35-in. (889 mm) tall 4-way multipoise condensing gas furnace
Table of Contents

Advertisement

Evaporator Coil
+
+
+
Condensing
+
Furnace
+
+
Blower
+ = Positive pressure
< + = Pressure lower than areas with +
(
= Negative pressure

To Relocate the Condensate Trap:

S Orient the furnace in the downflow position.
S Fig. 9 shows the condensate trap and tubing before and after
relocation. Refer to Fig. 9 to begin the trap conversion.
S Refer to Condensate Drain section for information how to install the
condensate drain.
Condensate Trap - - Horizontal Orientation.
When the furnace is installed in the horizontal right position, the
condensate trap will be initially located at the bottom of the collector
box, as received from the factory. See the top image in Fig. 10.
When the furnace is installed in the horizontal left position, the
condensate trap will be initially located at the top of the collector box,
as received from the factory. See the top image in Fig. 11. In both
cases the trap must be repositioned on the collector box for proper
condensate drainage. See the bottom images in Fig. 10 and 11.
A field- -supplied, accessory Horizontal Installation Kit
grommet) is required for all direct- -vent horizontal installations (only).
Air gap here
Open standpipe
for coil or
humidifier drain
TEE
(1/2" CPVC to 3/4" PVC
adapter from loose parts bag.)
To open drain
Open standpipe
(Optional when coil drain is
not connected to furnace
3/4" PVC
drain.)
+
+
+
3/4
+
3/4" PVC
3/4
+
+
3/4
1/2" CPVC or larger*
Recommend "T" fitting
high
< +
standpipe of same
< +
< +
diameteror larger
3/4
3/4
Fig. 12 - - Example of Field Drain Attachment
(trap
Ä Ä Ä Ä Ä Ä Ä Ä Ä Ä
Evaporator Coil
+ + +
Ä Ä Ä Ä Ä Ä Ä Ä Ä Ä
Ä Ä Ä Ä Ä Ä Ä Ä Ä Ä
Ä Ä Ä Ä Ä Ä Ä Ä Ä Ä
Ä Ä Ä Ä Ä Ä Ä Ä Ä Ä
Ä Ä Ä Ä Ä Ä Ä Ä Ä Ä
Ä Ä Ä Ä Ä Ä Ä Ä Ä Ä
Condensing
+
Furnace
+
+
Blower
-
- -
-
+ = Positive pressure
< + = Pressure lower than areas with +
= Negative pressure
Evaporator
Coil
Ä Ä Ä Ä Ä Ä Ä Ä Ä
+
Ä Ä Ä Ä Ä Ä Ä Ä Ä
+
Ä Ä Ä Ä Ä Ä Ä Ä Ä
Ä Ä Ä Ä Ä Ä Ä Ä Ä
+
Ä Ä Ä Ä Ä Ä Ä Ä Ä
Ä Ä Ä Ä Ä Ä Ä Ä Ä
Ä Ä Ä Ä Ä Ä Ä Ä Ä
Condensing
Furnace
+
+
+
Blower
-
- -
-
+ = Positive pressure
< + = Pressure lower than areas with +
= Negative pressure
The kit contains a rubber casing grommet designed to seal between
the furnace casing and the condensate trap. See Fig. 18.
To Relocate the Condensate Trap:
S Remove the knockout in the casing for the condensate trap.
S Install the grommet in the casing when required for direct- -vent
horizontal applications.
S Orient the furnace in the desired position.
S Allow for 2 in. (51 mm) of clearance underneath the furnace for the
condensate trap and drain line.
S Fig. 10 shows the condensate trap and tubing before and after
relocation in the horizontal right position.
S Fig. 11 shows the condensate trap and tubing before and after
relocation in the horizontal left position.
S Refer to the appropriate figure to begin the trap conversion.
S Refer to Condensate Drain section for information how to install the
condensate drain.
12
3/4" PVC
+
+
3/4
+
3/4" PVC
3/4
+
Open standpipe
Air gap required when
+
another drain is connected
+
to furnace drain.
3/4
TEE
(1/2" CPVC to 3/4" PVC
adapter from loose parts bag.)
< +
< +
< +
3/4
-
-
3/4
Open standpipe
(Optional when coil drain is
3/4" PVC
not connected to furnace
drain.)
3/4
+
+
3/4
3/4
3/4" PVC
TEE
3/4
(1/2" CPVC to 3/4" PVC
adapter from loose parts bag.)
< +
< +
< +
-
3/4
-
3/4
A170135

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents