Installation; Formed Rubber Drain Grommet; Drain Trap Connection And Routing; Modify Rubber Drain Elbow - Carrier 59TP6B Installation, Start-Up, Operating And Service And Maintenance Instructions

Two-stage variable speed ecm multipoise condensing gas furnace
Table of Contents

Advertisement

INSTALL CLAMPS ON DRAIN TUBE
ATTACH DRAIN TUBE TO CONDENSATE
DRAIN TRAP
OPEN SPRING CLAMP
INSERT FACTORY SUPPLIED 1/2 IN. CPVC
TO 3/4 IN. PVC ADAPTER OR 1/2 IN. CPVC PIPE
*CLAMP MAY BE LOCATED ON OUTSIDE OF DRAIN
TUBE
Fig. 15 - - Formed Rubber Drain Grommet
Fig. 16 - - Modify Rubber Drain Elbow
NOTE: Trap grommet is required only for direct-vent
applications.
Fig. 17 - - Horizontal Drain Trap Grommet
PULL DRAIN STUB
THROUGH CASING
Remove knockout.
Install grommet before
relocating condensate
trap.
FORMED END
OF GROMMET
FACTORY SUPPLIED
1/2 IN. CPVC TO 3/4 IN.
PVC ADAPTER
DRAIN ELBOW "Z" DISCHARGE PIPE FOR LEFT SIDE
FORMED END OF GROMMET. OPEN
SPRING CLAMP, INSERT 1/2 IN. TO 3/4 IN.
CPVC TO PVC ADAPTER OR CPVC PIPE
MODIFIED DRAIN ELBOW CON-
NECT TO CONDENSATE TRAP
AND 'Z' PIPE
LEFT SIDE DRAIN PIPE ORIENTATION FOR CONDENSATE DISCHARGE
NOTE: Remove Inducer Housing for easier access, if desired.
A11342A
Fig. 18 - - Drain Trap Connection and Routing
This furnace is certified to leak 2% or less of nominal air
conditioning CFM delivered when pressurized to 1- -in. water
column with all present air inlets, including bottom closure in
upflow and horizontal applications, air outlets, and plumbing
and electrical ports sealed.
Upflow Installation
NOTE: The furnace must be pitched as shown in Fig. 25 for
proper condensate drainage.
Supply Air Connections
A11581
For a furnace not equipped with a cooling coil, the outlet duct shall
be provided with a removable access panel. This opening shall be
accessible when the furnace is installed and shall be of such a size
that the heat exchanger can be viewed for possible openings using
light assistance or a probe can be inserted for sampling the air
stream. The cover attachment shall prevent leaks.
Connect supply- -air duct to flanges on furnace supply- -air outlet.
Bend flange upward to 90_ with wide duct pliers. See Fig. 22. The
supply- -air duct must be connected to ONLY the furnace
supply- -outlet- -air duct flanges or air conditioning coil casing
(when used). DO NOT cut main furnace casing side to attach
supply air duct, humidifier, or other accessories. All supply- -side
accessories MUST be connected to duct external to furnace main
casing.
A11582
20
ATTACH ELBOW TO
CONDENSATE TRAP
CUT FORMED END OFF
CONDENSATE DRAIN
ELBOW
CONNECT SHORT END OF
'Z' PIPE TO MODIFIED
DRAIN ELBOW
TOP VIEW
DRAIN IS ROUTED BEHIND INDUCER
FRONT VIEW
(Appearance may vary)

INSTALLATION