R ATIN G S
NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
88 kW - LGH300S4 (1ST STAGE)
18.3°C
Entering
Total
Wet
Air
Total
Comp.
Bulb
Volume
Cool
Motor
Temper-
Cap.
Input
ature
L/s
kW
kW
3775
38
5.26
17.2°C
4485
39.4
5.3
5190
40.5
5.34
3775
40.1
5.33
19.4°C
4485
41.4
5.37
5190
42.5
5.41
3775
42.5
5.41
21.7°C
4485
43.7
5.46
5190
44.7
5.5
88 kW - LGH300S4 (2ND STAGE)
26.7°C
Entering
Total
Wet
Air
Total
Comp.
Bulb
Volume
Cool
Motor
Temper-
Cap.
Input
ature
L/s
kW
kW
3775
73.2
14
17.2°C
4485
75.6
14.13
5190
77.8
14.25
3775
77.2
14.22
19.4°C
4485
79.5
14.35
5190
81.2
14.45
3775
81.5
14.46
21.7°C
4485
83.8
14.6
5190
85.5
14.69
48°C
Entering
Total
Wet
Air
Total
Comp.
Bulb
Volume
Cool
Motor
Temper-
Cap.
Input
ature
L/s
kW
kW
3775
60.2
21.98
17.2°C
4485
62.8
22.16
5190
64.9
22.29
3775
63.2
22.18
19.4°C
4485
64.9
22.29
5190
66.1
22.37
3775
66.7
22.43
21.7°C
4485
68.2
22.52
5190
69.4
22.62
Energence
Packaged Gas / Electric 45.7 to 88 kW - 50 Hz / Page 26
®
Outdoor Air Temperature Entering Outdoor Coil
23.9°C
Sensible To Total
Total
Comp.
Ratio (S/T)
Cool
Motor
Cap.
Input
Dry Bulb
24°C 27°C 29°C
kW
kW
0.72
0.87
0.99
36.3
5.94
0.76
0.93
1
37.6
5.99
0.81
0.98
1
38.6
6.03
0.57
0.7
0.84
38.2
6.02
0.59
0.74
0.9
39.6
6.07
0.62
0.79
0.96
40.4
6.1
0.43
0.56
0.68
40.5
6.1
0.44
0.58
0.72
41.7
6.15
0.44
0.61
0.76
42.6
6.19
Outdoor Air Temperature Entering Outdoor Coil
35°C
Sensible To Total
Total
Comp.
Ratio (S/T)
Cool
Motor
Cap.
Input
Dry Bulb
24°C 27°C 29°C
kW
kW
0.76
0.92
1
68.2
16.58
0.8
0.98
1
70.4
16.71
0.85
1
1
72.9
16.86
0.59
0.73
0.88
71.8
16.8
0.62
0.78
0.95
73.8
16.92
0.64
0.82
1
75.3
17.02
0.44
0.58
0.71
75.8
17.05
0.45
0.61
0.76
77.7
17.16
0.46
0.64
0.8
79.2
17.26
Outdoor Air Temperature Entering Outdoor Coil
50°C
Sensible To Total
Total
Comp.
Ratio (S/T)
Cool
Motor
Cap.
Input
Dry Bulb
24°C 27°C 29°C
kW
kW
.83
1.00
1.00
59.0
23.07
.90
1.00
1.00
61.6
23.26
.96
1.00
1.00
63.5
23.39
.63
.81
.99
61.8
23.27
.67
.87
1.00
63.3
23.37
.70
.94
1.00
64.6
23.46
.46
.63
.79
65.1
23.50
.48
.66
.85
66.7
23.61
.49
.70
.92
67.8
23.69
29.4°C
Sensible To Total
Total
Comp.
Ratio (S/T)
Cool
Motor
Cap.
Input
Dry Bulb
24°C 27°C 29°C
kW
kW
0.74
0.9
1
34.7
6.71
0.79
0.96
1
35.9
6.76
0.83
0.99
1
37
6.8
0.58
0.71
0.86
36.6
6.79
0.61
0.77
0.93
37.7
6.83
0.64
0.81
0.98
38.5
6.86
0.43
0.57
0.69
38.6
6.87
0.44
0.6
0.74
39.8
6.92
0.44
0.63
0.78
40.5
6.95
43.3°C
Sensible To Total
Total
Comp.
Ratio (S/T)
Cool
Motor
Cap.
Input
Dry Bulb
24°C 27°C 29°C
kW
kW
0.78
0.96
1
63.1
19.77
0.83
1
1
65.6
19.94
0.88
1
1
67.8
20.08
0.61
0.76
0.92
66.4
19.98
0.64
0.81
0.99
68.1
20.1
0.66
0.86
1
69.4
20.19
0.44
0.6
0.74
70
20.23
0.46
0.63
0.79
71.7
20.34
0.47
0.65
0.84
73.1
20.43
51.7°C
Sensible To Total
Total
Comp.
Ratio (S/T)
Cool
Motor
Cap.
Input
Dry Bulb
24°C 27°C 29°C
kW
kW
.84
1.00
1.00
58
24.1
.91
1.00
1.00
60.5
24.27
.97
1.00
1.00
62.4
24.4
.64
.82
1.00
60.4
24.25
.68
.88
1.00
62
24.38
.71
.95
1.00
63.2
24.45
.46
.63
.80
63.8
24.49
.48
.67
.86
65.4
24.61
.49
.70
.93
66.4
24.68
Sensible To Total
Total
Comp.
Ratio (S/T)
Cool
Motor
Cap.
Input
Dry Bulb
24°C 27°C 29°C
kW
kW
0.75
0.92
1
33.3
7.59
0.8
0.98
1
34.4
7.64
0.85
1
1
35.5
7.68
0.59
0.74
0.88
35
7.66
0.62
0.78
0.95
36
7.7
0.64
0.83
0.99
36.7
7.74
0.45
0.58
0.72
36.9
7.75
0.45
0.61
0.76
37.9
7.8
0.45
0.63
0.8
38.6
7.83
Sensible To Total
Total
Comp.
Ratio (S/T)
Cool
Motor
Cap.
Input
Dry Bulb
24°C 27°C 29°C
kW
kW
0.81
0.99
1
61.5
20.96
0.87
1
1
64.1
21.14
0.93
1
1
66.3
21.29
0.62
0.79
0.97
64.6
21.17
0.66
0.85
1
66.3
21.28
0.69
0.91
1
67.6
21.37
0.45
0.62
0.77
68.1
21.41
0.47
0.65
0.83
69.8
21.53
0.48
0.68
0.88
71.0
21.61
Sensible To Total
Ratio (S/T)
Dry Bulb
24°C 27°C 29°C
0.85
1
1
0.92
1
1
0.98
1
1
0.65
0.83
1
0.68
0.9
1
0.72
0.96
1
0.47
0.64
0.81
0.48
0.68
0.88
0.49
0.71
0.94
35°C
Sensible To Total
Ratio (S/T)
Dry Bulb
24°C
27°C
29°C
0.78
0.95
1
0.82
0.99
1
0.87
1
1
0.6
0.75
0.91
0.63
0.8
0.97
0.65
0.85
1
0.44
0.59
0.73
0.45
0.62
0.78
0.47
0.65
0.83
46°C
Sensible To Total
Ratio (S/T)
Dry Bulb
24°C
27°C
29°C
.84
1.00
1.00
.90
1.00
1.00
.95
1.00
1.00
.64
.82
.98
.67
.88
1.00
.71
.93
1.00
.46
.63
.80
.48
.67
.85
.49
.71
.91