NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
88 kW - LGH300S4 (1ST STAGE)
18.3°C
Entering
Total
Wet
Air
Total
Comp.
Bulb
Volume
Cool
Motor
Temper-
Cap.
Input
ature
L/s
kW
kW
3775
38
5.26
17.2°C
4485
39.4
5.3
5190
40.5
5.34
3775
40.1
5.33
19.4°C
4485
41.4
5.37
5190
42.5
5.41
3775
42.5
5.41
21.7°C
4485
43.7
5.46
5190
44.7
5.5
88 kW - LGH300S4 (2ND STAGE)
26.7°C
Entering
Total
Wet
Air
Total
Comp.
Bulb
Volume
Cool
Motor
Temper-
Cap.
Input
ature
L/s
kW
kW
3775
73.2
14
17.2°C
4485
75.6
14.13
5190
77.8
14.25
3775
77.2
14.22
19.4°C
4485
79.5
14.35
5190
81.2
14.45
3775
81.5
14.46
21.7°C
4485
83.8
14.6
5190
85.5
14.69
48°C
Entering
Total
Wet
Air
Total
Comp.
Bulb
Volume
Cool
Motor
Temper-
Cap.
Input
ature
L/s
kW
kW
3775
60.2
21.98
17.2°C
4485
62.8
22.16
5190
64.9
22.29
3775
63.2
22.18
19.4°C
4485
64.9
22.29
5190
66.1
22.37
3775
66.7
22.43
21.7°C
4485
68.2
22.52
5190
69.4
22.62
Energence
Packaged Gas / Electric 45.7 to 88 kW - 50 Hz / Page 26